Plan Review Notes For Permit 21010298 |
Permit Number |
21010298 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-01-12 09:02:46 | PLAN REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) PROVIDE DETAILS OF EXISTING GENERATOR PAD TO CONFIRM | | THAT IT IS COMPATIBLE WITH THE NEW GENERATOR. FBC | | 107.2.1 | | | | 2) PROVIDE GENERATOR TO PAD ANCHORING DETAILS. SPECIFY | | THE NUMBER, LOCATIONS AND TYPE OF FASTENERS. FBC 107.2 | | | | 3) PLEASE PROVIDE A RESPONSE LETTER INDICATING HOW THE | | COMMENTS WILL BE ADDRESSED. | | | | |
|