Plan Review Notes For Permit 21010260 |
Permit Number |
21010260 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-01-22 13:21:26 | ROOFING | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) DRAWINGS FOR PERMIT 20020932 DO NOT SHOW A FLAT | | ROOF. PLEASE PROVIDE A SITE PLAN SHOWING THE LOCATION | | OF THE FLAT ROOF TO BE INSTALLED. | | 2) ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT | | APPROVAL REQUIRES ADDITIONAL SIGNED AND SEALED | | ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR | | ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A HIGHER PRESSURE | | THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL (-52.5) | | - SEE GENERAL LIMITATION NOTE NUMBER 7 ON THE PRODUCT | | APPROVAL. | | 3) PLEASE PROVIDE THE ADDITIONAL JOB COST ON THE | | REVISION FORM. | | |
|