2021-03-29 11:06:15 | NEW SFR |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected]. |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENTS |
| |
| NO CHANGES SINCE THE LAST REVIEW |
| |
| CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| 1) PLEASE SHOW CARBON MONOXIDE DETECTOR LOCATION TO |
| COMPLY WITH FBC R315.1 CARBON MONOXIDE PROTECTION. |
| EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING |
| BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS |
| ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR |
| APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER |
| FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE |
| AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL |
| CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH |
| ROOM USED FOR SLEEPING PURPOSES. |
| 2) PLEASE SHOW SMOKE ALARM LOCATIONS TO COMPLY WITH FBC |
| R314.3 (SHOW SMOKE ALARM OUTSIDE OF MASTER RETREAT IN |
| THE MASTER RETREAT VESTIBULE - SMOKE ALARM SHOULD NOT |
| BE IN THE MASTER RETREAT BATH ROOM. |
| 3) PLEASE SHOW A BATH/TOILET ROOM DOOR WIDTH OF A CLEAR |
| OPENING OF 29 INCHES ON THE FIRST FLOOR TO COMPLY WITH |
| FBC R320.1.1 - FBC ACCESSIBILITY 404.2.3 CLEAR WIDTH. |
| CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE |
| MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP, |
| WITH THE DOOR OPEN 90 DEGREES. |
| 4) PLEASE SHOW THE GARAGE CEILING FIRE PROTECTION FROM |
| HABITABLE ROOMS ABOVE THE GARAGE PER FBC R302.6 (5/8 |
| TYPE X DRYWALL). |
| 5) PLEASE SHOW THE REQUIRED DRYWALL UNDER THE ENCLOSED |
| STAIR TO COMPLY WITH FBC R302.7 UNDER-STAIR PROTECTION. |
| ENCLOSED SPACE UNDER STAIRS THAT IS ACCESSED BY A DOOR |
| OR ACCESS PANEL SHALL HAVE WALLS, UNDER-STAIR SURFACE |
| AND ANY SOFFITS PROTECTED ON THE ENCLOSED SIDE WITH |
| 1/2-INCH (12.7 MM) GYPSUM BOARD. |
| 6) PLEASE SHOW THE CEILING/FLOOR ASSEMBLY DRAFT |
| STOPPING TO COMPLY WITH FBC R302.12 DRAFTSTOPPING. |
| IN COMBUSTIBLE CONSTRUCTION WHERE THERE IS USABLE SPACE |
| BOTH ABOVE AND BELOW THE CONCEALED SPACE OF A |
| FLOOR-CEILING ASSEMBLY, DRAFTSTOPS SHALL BE INSTALLED |
| SO THAT THE AREA OF THE CONCEALED SPACE DOES NOT EXCEED |
| 1,000 SQUARE FEET (92.9 M2). DRAFTSTOPPING SHALL DIVIDE |
| THE CONCEALED SPACE INTO APPROXIMATELY EQUAL AREAS. |
| WHERE THE ASSEMBLY IS ENCLOSED BY A FLOOR MEMBRANE |
| ABOVE AND A CEILING MEMBRANE BELOW, DRAFTSTOPPING SHALL |
| BE PROVIDED IN FLOOR-CEILING ASSEMBLIES UNDER THE |
| FOLLOWING CIRCUMSTANCES: |
| 1.CEILING IS SUSPENDED UNDER THE FLOOR FRAMING. |
| 2.FLOOR FRAMING IS CONSTRUCTED OF TRUSS-TYPE OPEN-WEB |
| OR PERFORATED MEMBERS. |
| 7) PLEASE SHOW THE FLAT ROOF FRAMING DETAILS - JOIST |
| SIZE, SPACING AND ATTACHMENTS, STRAPPING ETC. |
| 8) ALL PRODUCT APPROVALS PROVIDED NEED TO BE REVIEWED |
| AND MARKED APPROVED BY THE BUILDING DESIGNER OF RECORD |
| OR BE LISTED BY PRODUCT APPROVAL NUMBER ON THE |
| DRAWINGS. |
| 9) PRODUCT APPROVAL PROVIDED FOR THE METAL ROOFING |
| SYSTEM (-89.4) DOES NOT MEET THE REQUIRED WIND DESIGN |
| PRESSURES FOR ROOF WIND ZONES 3 (-99.22) - ROOF |
| CLADDING DESIGN PRESSURES ARE NOT SHOWN ON THE DRAWINGS |
| - WIND PRESSURES ARE BASED ON FBC TABLER301.2(2) |
| 10) PLEASE PROVIDE A MIAMI DADE OR FLORIDA STATE |
| PRODUCT APPROVAL FOR THE FLAT DECK ROOFING = PLEASE |
| CIRCLE THE ROOFING SYSTEM TO BE USED IN THE PRODUCT |
| APPROVAL - IF NEEDED PLEASE PROVIDE SIGNED AND SEALED |
| ADDITIONAL ATTACHMENT DETAILS FROM AN ARCHITECT OR |
| ENGINEER FOR THE ROOF ZONES 2 AND 3 WHICH MAY REQUIRE A |
| HIGHER WIND PRESSURE - SEE NOTES ON THE PRODUCT |
| APPROVAL. |
| 11) PLEASE PROVIDE THE FLORIDA STATE PRODUCT APPROVAL |
| FRONT PAGES FOR (DOOR - FL17347 AND METAL ROOF - |
| FL11560.4). THE INSTALLATION INSTRUCTIONS HAVE BEEN |
| PROVIDED. |
| 12) ROOFING SYSTEM AND WINDOW AND DOOR PRODUCT |
| APPROVALS MAY BE DEFERRED SUBMITTALS BY LISTING ITEMS |
| TO BE DEFERRED ON THE CONSTRUCTION DOCUMENTS - |
| 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR |
| DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE |
| REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING |
| OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE |
| IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING. |
| THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED |
| UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN |
| APPROVED BY THE BUILDING OFFICIAL. |
| |