Plan Review Notes For Permit 21010248 |
Permit Number |
21010248 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-01-27 15:02:31 | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | NO RISER DIAGRAM SHOWN 215.5 | | | | NO LOAD CALCULATION SHOWN 220 | | | | NO PANEL SCHEDULE SHOWN | | PROVIDE PANEL SCHEDULE INDICATING NEW CIRCUITS, THE | | WIRE AND BREAKER SIZE FOR THESE CIRCUITS, AND AFCI OR | | GFCI PROTECTION WHERE APPLICABLE TO COMPLY WITH CODE. | | NEC 210.8, 210.12, 215.5, 408.4 | | | | ALL RECPTACLES INSTALLED OUTSIDE AT 120 VOLTS 15 AND 20 | | A TO BR GFCI PROTECTED PER 210.8(A) | | | | |
|