2021-01-27 15:02:31FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO RISER DIAGRAM SHOWN 215.5
  
 NO LOAD CALCULATION SHOWN 220
  
 NO PANEL SCHEDULE SHOWN
 PROVIDE PANEL SCHEDULE INDICATING NEW CIRCUITS, THE
 WIRE AND BREAKER SIZE FOR THESE CIRCUITS, AND AFCI OR
 GFCI PROTECTION WHERE APPLICABLE TO COMPLY WITH CODE.
 NEC 210.8, 210.12, 215.5, 408.4
  
 ALL RECPTACLES INSTALLED OUTSIDE AT 120 VOLTS 15 AND 20
 A TO BR GFCI PROTECTED PER 210.8(A)
  
  