2021-01-26 12:27:44WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21010228
 ADD: 700 S. ROSEMARY AVE.
 CONT: BUTLER CONSTRUCTION CO.
 TEL: 561-832-9700
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JAN. 26TH/2021
 ACTION: DENIED
  
 1) PLEASE PROVIDE A SURVEY OF THE EXISTING COLUMNS IN
 RELATIONSHIP TO THE NEW COLUMN DESIGN AND THE PROPERTY
 LINE. THE OTHER ISSUE IS THE RELATIONSHIP (DISTANCE)
 FROM THE PROPERTY LINE AND THE PROPOSED ALUMINUM
 FRAMEWORK. 2020 FBC-B. CHAPTER 32 ENCROACHMENTS INTO
 THE RIGHT OF WAY. THE 2020 FBC-B SECTIONS 3202.2.2,
 3202.3.2 & 3202.3 DO ALLOW FOR ARCHITECTURAL FEATURES
 BEYOND THE LOT LINE ABOVE GRADE DEPENDING ON THEIR
 HEIGHT ABOVE GRADE.
  
 2) PLEASE CONTACT THE ENGINEERING DEPARTMENT, A RIGHT
 OF WAY PERMIT MAY NEED TO BE OBTAINED TO DO WORK, OR
 SET UP SCAFFOLDING IN THE RIGHT OF WAY. MAIN PHONE:
 (561) 822-1200. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 3A) NEITHER THE COVERSHEET, INDEX SHEET NOR THE 1ST
 ELEVATION SHEET A1.1.1 INDICATE THE MINIMUM
 CONSTRUCTION TYPE.
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATIVE CODE SECTION:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND
 OR STRUCTURES.
 107.3.5.1 COMMERCIAL BUILDINGS
 107.3.5.1.1. BUILDING
 MINIMUM TYPE OF CONSTRUCTION
 PLEASE NOTE WHEN CITY PLACE WAS BUILT THE MINIMUM
 CONSTRUCTION TYPE IS II-B CONSTRUCTION.
  
 3B) SHEET A4.0.1 WALL SECTIONS 1, 2 & 3 ALL STATE THE
 NEW COLUMNS ARE TO BE CLAD WITH STRUCTURAL SHEATHING.
 THE TYPE OF SHEATHING NOR THICKNESS OF THE SHEATHING IS
 NOT NAMED. SHEET A5.0.1 THE RENDERING STATES PLYWOOD
 SUBSTRATE. THE STRUCTURAL SHEETS DO NOT CALL OUT THE
 SUB-SHEATHING EITHER. PLEASE REFER TO THE 2020 FBC-B
 SECTION 603.1.1.2 FIRE RETARDANT TREATED WOOD SHALL BE
 PERMITTED IN : 1.2 NONBEARING EXTERIOR WALLS WHERE FIRE
 RESISTANCE RATED CONSTRUCTION IS NOT REQUIRED.
  
 3C) SHEET A4.0.1 WALL SECTIONS 2 & 3 BOTH SHOW NEW ROOF
 FRAMING MEMBERS AND SHEATHING, AGAIN THE TYPE OF
 SHEATHING IS NOT CALLED OUT. SHEET S4.00 THE ROOF
 SECTION DOES CALL OUT ? INCH FRT PLYWOOD FOR THE ROOF
 TOP DECKING BUT THE FRONT WALL EXTENSION THE PLYWOOD IS
 LISTED AS ? INCH STRUCTURAL SHEATHING NOT FIRE
 RETARDANT TREATED PLYWOOD. 2020 FBC-B SECTION 603.1.1.2
 FIRE RETARDANT TREATED WOOD SHALL BE PERMITTED IN : 1.2
 NONBEARING EXTERIOR WALLS WHERE FIRE RESISTANCE RATED
 CONSTRUCTION IS NOT REQUIRED.
  
 4A) SHEET A4.0.1 DETAILS 2 & 3 BOTH SHOW A NEW FLAT
 ROOF SECTION PLEASE SHOW COMPLIANCE WITH THE 2020 FBC-B
 SECTIONS 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31) (D) ROOFING PRODUCTS AND ASSEMBLIES.
  
 4B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 4C) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 5) SHEET A4.0.1. SHOWS A DECORATIVE ALUMINUM FRAME TO
 BE DESIGNED BY A DELEGATED FABRICATOR, THIS CAN BE A
 DEFERRED SUBMITTAL. DELEGATED ENGINEERING. 61G15-30.003
 ENGINEERING DOCUMENT CLASSIFICATION. FL 61G-15-30.006
 (3) THE DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 6) THE ARCHITECTURAL AND STRUCTURAL SHEETS BOTH SHOW
 THE USE OF EITHER WELDED AND OR BOLTED STEEL
 CONNECTIONS. WELDED OR BOLTED CONNECTIONS. THE
 CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED. REPORTS SUBMITTED TO BUILDING INSPECTOR AT
 TIME OF FRAMING INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2020 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
  
 7) SHEET A4.01 DETAILS INDICATE THE USE OF IRONSPOT
 BRICK VENEER CLADDING, PLEASE PROVIDE COMPLIANCE WITH
 1405.10.1.4 ADHERED MASONRY VENEERS. PLEASE PROVIDE
 INSTALLATION INSTRUCTIONS AND LIMITATIONS FOR THIS
 PRODUCT.
  
 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  