Plan Review Notes
Plan Review Notes For Permit 21010114
Permit Number 21010114
Review Stop B
Sequence Number 1
Notes
Date Text
2021-03-23 07:39:26PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD DRAWING REFERENCES THE FBC SIXTH
 EDITION (2017) AND ASCE 7-10. THE FBC SEVENTH EDITION
 (2020) WENT INTO EFFECT ON DECEMBER 31, 2020 AND
 REFERENCES ASCE 7-16. ALL NEW PERMITS APPLIED FOR ON OR
 AFTER THAT DATE ARE REQUIRED TO COMPLY WITH AND
 REFERENCE THE 2020 FBC SEVENTH EDITION AND ASCE 7-16.
 FS CHAPTER 553
  
 2) THE NOTES ON THE SURVEY INDICATE THAT THE GENERATOR
 IS TO BE LOCATED 5 FEET FROM WINDOWS. THE GENERATOR
 EXHAUST IS REQUIRED TO BE 10 FEET FROM ANY OPENINGS
 INTO A STRUCTURE. FBC-R303.5.1 MECHANICAL AND GRAVITY
 OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS
 THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS
 CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS,
 STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS.
  
 3) A VERIFIABLE DIGITAL SIGNATURE IS REQUIRED ON
 ELECTRONICALLY SUBMITTED DRAWINGS. SEE SIGNATURE REVIEW
 COMMENTS.
  
  