2021-06-03 13:06:43 | 2ND REVIEW FBC-2020 RES. |
| PERMIT- 21010112 |
| 6/3/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. THE 1ST REVIEW COMMENT |
| LISTED BELOW STILL EXISTS. THE ENGINEER'S COPIED SEAL |
| HAS BEEN REMOVED FROM THE TIE DOWN ENGINEERING ABOVE |
| GROUND TANK ANCHORAGE DETAILS HOWEVER THE SHEETS ARE |
| STILL BEARING THE TIE- DOWN ENGINEERING TITLE BLOCK AND |
| A BLOCK FOR THE ENGINEER?S SEAL. AS NOTED IN THE 1ST |
| REVIEW THE DETAIL DOES NOT MATCH THE RISER DRAWING |
| WHICH SPECIFIES AN UNDERGROUND (UG) TANK. |
| |
| 1) SUBMIT LP TANK HOLD DOWN DETAILS- SECTION 6.6.1.6 |
| NFPA 58. SHOW HOW THE TANK WILL BE ANCHORED TO PREVENT |
| FLOTATION, COLLAPSE, OR LATERAL MOVEMENT. PLEASE |
| INCLUDE A FRONT AND SIDE ELEVATION VIEW THAT SHOWS THE |
| BURIAL DEPTH, ANCHORING BASE MATERIAL, AND THE TYPES, |
| SIZES, AND NUMBERS OF ANCHORS, CABLES OR STRAPS, AND |
| THE TYPE OF PROTECTIVE SLEEVES FOR THE CABLES OR |
| STRAPS. THE DETAIL SUBMITTED IS FOR AN ABOVE GROUND |
| TANK. |
| PLEASE NOTE THAT HOLD DOWN DETAILS PROVIDED BY A |
| LICENSED ENGINEER SHALL BEAR THE DIGITAL SIGNATURE AND |
| SEAL OF THE ENGINEER-- FL. STATUTE 471.025 AND SECTION |
| 61G15-23.005 FAC. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |