Plan Review Notes
Plan Review Notes For Permit 21010112
Permit Number 21010112
Review Stop G
Sequence Number 1
Notes
Date Text
2021-01-25 10:49:291ST REVIEW FBC-2020 RES.
 PERMIT- 21010112
 1/25/2012
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT LP TANK HOLD DOWN DETAILS- SECTION 6.6.1.6
 NFPA 58. SHOW HOW THE TANK WILL BE ANCHORED TO PREVENT
 FLOTATION, COLLAPSE, OR LATERAL MOVEMENT. PLEASE
 INCLUDE A FRONT AND SIDE ELEVATION VIEW THAT SHOWS THE
 BURIAL DEPTH, ANCHORING BASE MATERIAL, AND THE TYPES,
 SIZES, AND NUMBERS OF ANCHORS, CABLES OR STRAPS, AND
 THE TYPE OF PROTECTIVE SLEEVES FOR THE CABLES OR
 STRAPS. THE DETAIL SUBMITTED IS FOR AN ABOVE GROUND
 TANK.
  
 PLEASE NOTE THAT HOLD DOWN DETAILS PROVIDED BY A
 LICENSED ENGINEER SHALL BEAR THE DIGITAL SIGNATURE AND
 SEAL OF THE ENGINEER-- FL. STATUTE 471.025 AND SECTION
 61G15-23.005 FAC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  