Notes |
Date |
Text |
2021-02-12 09:11:10 | THE PREVIOUS COMMENT HAS NOT BEEN ADDRESSED. THE | | GENERATOR PAD ENGINEERING SHOULD BE UPLOADED AS A | | SEPARATE FILE WITH A VALID DIGITAL SIGNATURE. | | | | I WAS NOT ABLE TO VERIFY THE ENGINEER'S DIGITAL | | SIGNATURE ON THE PRE-FAB GENERATOR PAD DRAWING. IT IS | | THE LAST PAGE OF THE GENERATOR SPECS. ELECTRONICALLY | | SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ENGINEER'S | | DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO | | SUBMIT THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS. | | AFTER THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN | | SUBMIT THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING | | DEPARTMENT TO BE VERIFIED. THE ENGINEER'S ORIGINAL | | HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE | | DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE | | SIGNATURE ARE ACCEPTABLE. FS 471 & 61G15 |
|