Plan Review Notes For Permit 21010110 |
Permit Number |
21010110 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-01-11 08:01:35 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) REVISE NOTE ON SURVEY TO REQUIRE THAT GENERATOR | | EXHAUST IS TO BE 10' FROM ANY OPENINGS. FBC-R303.5.1 | | INTAKE OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR | | INTAKE OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET | | (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, | | SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, | | ALLEYS, PARKING LOTS AND LOADING DOCKS. | | |
|