2021-03-24 16:51:52 | 1ST REVIEW FBC- 2020 PLUMBING |
| PERMIT- 21010157 |
| 1/20/21 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET A3.0: THE FINISH SCHEDULE SHOWS GYPSUM WALL |
| BOARD AND EPOXY PAINT FOR THE NEW MOP SINK WALL |
| SURROUND WHICH IS NOT CODE COMPLIANT. PLEASE REFER TO |
| SECTION 1210.2.2 FBC B: WALLS AND PARTITIONS WITHIN 2 |
| FEET OF SERVICE SINKS, URINALS AND WATER CLOSETS SHALL |
| HAVE SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT OF |
| NOT LESS THAN 4 FEET ABOVE THE FLOOR, AND EXCEPT FOR |
| STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS |
| SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY |
| MOISTURE. |
| |
| 2) P-0.1: PLEASE PROVIDE A SLAB REPAIR DETAIL FOR THE |
| NEW MOP SINK DRAIN INSTALLATION- SECTION 107.2.1 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |