2021-01-20 08:47:24 | 1ST REVIEW FBC- 2020 PLUMBING |
| PERMIT- 21010157 |
| 1/20/21 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEETS A.01: PROVIDE ADDITIONAL PLUMBING DEMOLITION |
| NOTES AND DETAILS- SECTION 107.2.1 WPB. |
| |
| A) SHOW THE EXTENT OF DEMOLITION FOR UNDER SLAB |
| SANITARY DRAINAGE PIPES AND WHERE CAPS OR CLEANOUTS |
| WILL BE INSTALLED. |
| |
| B) SHOW THE EXTENT OF DEMOLITION FOR WATER SUPPLY LINES |
| AND WHERE CAPS OR VALVES WILL BE INSTALLED. |
| |
| C) PLEASE PROVIDE DEMOLITION NOTES FOR THE TOILET ROOM |
| SHOWN IN THE TENANT SPACE BY GRIDLINE F. |
| |
| 2) SHEET A1.0: PLEASE PROVIDE PLUMBING FIXTURE |
| CALCULATIONS FOR THE RE-CONFIGURED TENANT SPACE IN |
| COMPLIANCE WITH TABLE 403.1 FBC P. PLEASE NOTE THAT |
| SERVICE SINKS ARE REQUIRED FOR BUSINESS AND STORAGE |
| OCCUPANCIES. |
| |
| 3) A1.0: PLEASE SHOW THE CLEAR FLOOR SPACE APPROACH |
| DIAGRAM AND DIMENSIONS FOR THE BREAK ROOM SINK- SECTION |
| 305 FBC ACC. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |