Plan Review Notes For Permit 21010062 |
Permit Number |
21010062 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-01-20 16:09:28 | THE FOLLOWING COMMENTS ARE FOR INFORMATIONAL PURPOSES | | AND IN AN EFFORT TO REDUCE INTENTIONAL/ACCIDENTAL FALSE | | FIRE ALARMS. | | | | 1) PULL STATIONS ARE NOTED AT EVERY STAIRWELL; HOWEVER, | | THEY ARE NOT REQUIRED WHERE THE SPRINKLER SYSTEM | | ACTIVATES THE FA. | | | | PER NFPA 101, CH 42 | | | | 42.8.3.4.2 INITIATION. INITIATION OF THE REQUIRED FIRE | | ALARM SYSTEM | | SHALL BE BY ONE OF THE FOLLOWING MEANS: | | (1) MANUAL MEANS IN ACCORDANCE WITH 9.6.2.1(1) | | (2) APPROVED AUTOMATIC FIRE DETECTION SYSTEM IN | | ACCORDANCE WITH | | 9.6.2.1(2) THROUGHOUT THE BUILDING, PLUS A MINIMUM OF | | ONE | | MANUAL FIRE ALARM BOX IN ACCORDANCE WITH 9.6.2.6 | | (3) APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN | | ACCORDANCE WITH 9.6.2.1(3) THROUGHOUT THE BUILDING, | | PLUS A | | MINIMUM OF ONE MANUAL FIRE ALARM BOX IN ACCORDANCE WITH | | 9.6.2.6 | | | | 9.6.2.6* FOR FIRE ALARM SYSTEMS USING AUTOMATIC FIRE | | DETECTION OR | | WATERFLOW DETECTION DEVICES TO INITIATE THE FIRE ALARM | | SYSTEM IN | | ACCORDANCE WITH CHAPTERS 11 THROUGH 43, NOT LESS THAN | | ONE MANUAL | | FIRE ALARM BOX, LOCATED AS REQUIRED BY THE AUTHORITY | | HAVING | | JURISDICTION, SHALL BE PROVIDED TO INITIATE A FIRE | | ALARM SIGNAL. | | | | CONSIDER 1 PULL STATION NEAR THE ELECTRICAL ROOM. | | | | COORDINATE THE LOCATION THRU THE OFFICE OF THE FIRE | | MARSHAL UNLESS THE OWNER/EOR REQUEST THEM THROUGHOUT. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|