Plan Review Notes
Plan Review Notes For Permit 21010062
Permit Number 21010062
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-01-20 16:09:28THE FOLLOWING COMMENTS ARE FOR INFORMATIONAL PURPOSES
 AND IN AN EFFORT TO REDUCE INTENTIONAL/ACCIDENTAL FALSE
 FIRE ALARMS.
  
 1) PULL STATIONS ARE NOTED AT EVERY STAIRWELL; HOWEVER,
 THEY ARE NOT REQUIRED WHERE THE SPRINKLER SYSTEM
 ACTIVATES THE FA.
  
 PER NFPA 101, CH 42
  
 42.8.3.4.2 INITIATION. INITIATION OF THE REQUIRED FIRE
 ALARM SYSTEM
 SHALL BE BY ONE OF THE FOLLOWING MEANS:
 (1) MANUAL MEANS IN ACCORDANCE WITH 9.6.2.1(1)
 (2) APPROVED AUTOMATIC FIRE DETECTION SYSTEM IN
 ACCORDANCE WITH
 9.6.2.1(2) THROUGHOUT THE BUILDING, PLUS A MINIMUM OF
 ONE
 MANUAL FIRE ALARM BOX IN ACCORDANCE WITH 9.6.2.6
 (3) APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH 9.6.2.1(3) THROUGHOUT THE BUILDING,
 PLUS A
 MINIMUM OF ONE MANUAL FIRE ALARM BOX IN ACCORDANCE WITH
 9.6.2.6
  
 9.6.2.6* FOR FIRE ALARM SYSTEMS USING AUTOMATIC FIRE
 DETECTION OR
 WATERFLOW DETECTION DEVICES TO INITIATE THE FIRE ALARM
 SYSTEM IN
 ACCORDANCE WITH CHAPTERS 11 THROUGH 43, NOT LESS THAN
 ONE MANUAL
 FIRE ALARM BOX, LOCATED AS REQUIRED BY THE AUTHORITY
 HAVING
 JURISDICTION, SHALL BE PROVIDED TO INITIATE A FIRE
 ALARM SIGNAL.
  
 CONSIDER 1 PULL STATION NEAR THE ELECTRICAL ROOM.
  
 COORDINATE THE LOCATION THRU THE OFFICE OF THE FIRE
 MARSHAL UNLESS THE OWNER/EOR REQUEST THEM THROUGHOUT.
  
  