Date |
Text |
2021-01-26 16:18:58 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) SHEET FA 2 - THERE APPEARS TO BE 30CD IN THE |
| RESTROOM STALLS, WHERE ON 15CD MAY BE REQUIRED. |
| |
| PLEASE REVIEW AND CORRECT IF APPLICABLE. |
| |
| |
| 2) SHEET FA 2 - THERE APPEARS TO BE 75CD IN THE SINGLE |
| RESTROOMS 1140 & 1141, WHERE ON 15CD MAY BE REQUIRED. |
| |
| PLEASE REVIEW AND CORRECT IF APPLICABLE. |
| |
| |
| |
| 3) SHEET FA 2 - THERE APPEARS TO BE 75CD IN THE SINGLE |
| RESTROOMS 1204, WHERE ON 15CD MAY BE REQUIRED. |
| |
| PLEASE REVIEW AND CORRECT IF APPLICABLE. |
| |
| |
| |
| |
| 4) SHEET FA 3 - IN THE ROOM LOCATED IN THE LOWER LEFT |
| CORNER, THERE ARE NO INDICATIONS OF NOTIFICIATION AND |
| SA DEVICES. |
| |
| PLEASE REVIEW AND CORRECT. |
| |
| |
| |
| 5) SHEET FA 9 - AMPLIFIER LOADS IN THE CALCS SHOULD BE |
| LABELED IN WATTS NOT AMPS |
| |
| PLEASE REVIEW AND CORRECT IF APPLICABLE. |
| |
| |
| 6) ALL FLOOR PLAN SHEETS - WHERE ROOMS ARE CONNECTED |
| WITH A DOOR BEWTWEEN THEM THE SA SHALL BE |
| INTERCONNECTED. |
| |
| THERE ARE NO INDICATIONS THAT THE SA IN THE ADJACENT |
| SUITES ARE INTERCONNECTED. |
| |
| PER NFPA 101, CH 9 |
| |
| 9.6.2.10.3* THE INTERCONNECTION OF SMOKE ALARMS SHALL |
| APPLY ONLY |
| TO NEW CONSTRUCTION AS PROVIDED IN 9.6.2.10.8. |
| |
| 9.6.2.10.8* IN NEW CONSTRUCTION, WHERE TWO OR MORE |
| SMOKE ALARMS |
| ARE REQUIRED WITHIN A DWELLING UNIT, SUITE OF ROOMS, OR |
| SIMILAR AREA, |
| THEY SHALL BE ARRANGED SO THAT OPERATION OF ANY SMOKE |
| ALARM SHALL |
| CAUSE THE ALARM IN ALL SMOKE ALARMS WITHIN THE DWELLING |
| UNIT, SUITE |
| OF ROOMS, OR SIMILAR AREA TO SOUND, UNLESS OTHERWISE |
| PERMITTED BY |
| ONE OF THE FOLLOWING: |
| |
| (1) THE REQUIREMENT OF 9.6.2.10.8 SHALL NOT APPLY WHERE |
| PERMITTED BY ANOTHER SECTION OF THIS CODE. |
| (2) THE REQUIREMENT OF 9.6.2.10.8 SHALL NOT APPLY TO |
| CONFIGURATIONS THAT PROVIDE EQUIVALENT DISTRIBUTION OF |
| THE |
| ALARM SIGNAL. |
| 9.6.2.10.9 THE ALARMS DESCRIBED IN 9.6.2.10.8 SHALL |
| SOUND ONLY |
| WITHIN AN INDIVIDUAL DWELLING UNIT, SUITE OF ROOMS, OR |
| SIMILAR AREA |
| AND SHALL NOT ACTUATE THE BUILDING FIRE ALARM SYSTEM, |
| UNLESS |
| OTHERWISE PERMITTED BY THE AUTHORITY HAVING |
| JURISDICTION. |
| |
| PLEASE REVIEW AND CORRECT AND PROVIDE A NOTE OF |
| ACKNOWLEDGEMENT IN THOSE ROOMS. |
| |
| |
| |
| 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |