Plan Review Notes
Plan Review Notes For Permit 21010058
Permit Number 21010058
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-01-26 16:18:58THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET FA 2 - THERE APPEARS TO BE 30CD IN THE
 RESTROOM STALLS, WHERE ON 15CD MAY BE REQUIRED.
  
 PLEASE REVIEW AND CORRECT IF APPLICABLE.
  
  
 2) SHEET FA 2 - THERE APPEARS TO BE 75CD IN THE SINGLE
 RESTROOMS 1140 & 1141, WHERE ON 15CD MAY BE REQUIRED.
  
 PLEASE REVIEW AND CORRECT IF APPLICABLE.
  
  
  
 3) SHEET FA 2 - THERE APPEARS TO BE 75CD IN THE SINGLE
 RESTROOMS 1204, WHERE ON 15CD MAY BE REQUIRED.
  
 PLEASE REVIEW AND CORRECT IF APPLICABLE.
  
  
  
  
 4) SHEET FA 3 - IN THE ROOM LOCATED IN THE LOWER LEFT
 CORNER, THERE ARE NO INDICATIONS OF NOTIFICIATION AND
 SA DEVICES.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 5) SHEET FA 9 - AMPLIFIER LOADS IN THE CALCS SHOULD BE
 LABELED IN WATTS NOT AMPS
  
 PLEASE REVIEW AND CORRECT IF APPLICABLE.
  
  
 6) ALL FLOOR PLAN SHEETS - WHERE ROOMS ARE CONNECTED
 WITH A DOOR BEWTWEEN THEM THE SA SHALL BE
 INTERCONNECTED.
  
 THERE ARE NO INDICATIONS THAT THE SA IN THE ADJACENT
 SUITES ARE INTERCONNECTED.
  
 PER NFPA 101, CH 9
  
 9.6.2.10.3* THE INTERCONNECTION OF SMOKE ALARMS SHALL
 APPLY ONLY
 TO NEW CONSTRUCTION AS PROVIDED IN 9.6.2.10.8.
  
 9.6.2.10.8* IN NEW CONSTRUCTION, WHERE TWO OR MORE
 SMOKE ALARMS
 ARE REQUIRED WITHIN A DWELLING UNIT, SUITE OF ROOMS, OR
 SIMILAR AREA,
 THEY SHALL BE ARRANGED SO THAT OPERATION OF ANY SMOKE
 ALARM SHALL
 CAUSE THE ALARM IN ALL SMOKE ALARMS WITHIN THE DWELLING
 UNIT, SUITE
 OF ROOMS, OR SIMILAR AREA TO SOUND, UNLESS OTHERWISE
 PERMITTED BY
 ONE OF THE FOLLOWING:
  
 (1) THE REQUIREMENT OF 9.6.2.10.8 SHALL NOT APPLY WHERE
 PERMITTED BY ANOTHER SECTION OF THIS CODE.
 (2) THE REQUIREMENT OF 9.6.2.10.8 SHALL NOT APPLY TO
 CONFIGURATIONS THAT PROVIDE EQUIVALENT DISTRIBUTION OF
 THE
 ALARM SIGNAL.
 9.6.2.10.9 THE ALARMS DESCRIBED IN 9.6.2.10.8 SHALL
 SOUND ONLY
 WITHIN AN INDIVIDUAL DWELLING UNIT, SUITE OF ROOMS, OR
 SIMILAR AREA
 AND SHALL NOT ACTUATE THE BUILDING FIRE ALARM SYSTEM,
 UNLESS
 OTHERWISE PERMITTED BY THE AUTHORITY HAVING
 JURISDICTION.
  
 PLEASE REVIEW AND CORRECT AND PROVIDE A NOTE OF
 ACKNOWLEDGEMENT IN THOSE ROOMS.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  