Date |
Text |
2021-02-02 09:54:47 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 21010035 |
| ADD: 515 N. FLAGLER DR. SUITE: 801 |
| CONT: FINE LINE CONSTRUCTION |
| TEL: 561-582-7880 |
| E-MAIL: ASTEINBORG@FINELINE CONTRACTORS.COM |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| 1ST REVIEW |
| DATE: TUES. JAN. 19TH/2021 |
| ACTION: DENIED |
| |
| 1) SEMI-COMPLIED. LIFE SAFETY PLAN CORRECTED. SHEETS |
| A1, A2, A3, A4, E1, E2, M1 & P1 NOT CORRECTED. |
| DISCREPANCY IN PLANS. |
| PLEASE CORRECT THE LABELING OF KITCHENS AND STORAGE |
| ROOM. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 1ST ROUND OF COMMENTS. THE LIFE SAFETY SHEET SHOWS |
| TRAVEL DISTANCES IN THE WORK WHERE THE NEW WORK IS |
| PROPOSED, BUT NOT ON THE OTHER SIDE OF THE NEW WALL |
| (EXISTING KITCHEN) THAT CREATES DEAD END CORRIDORS & |
| EGRESS THROUGH A KITCHEN AND CLOSET. NOTE THE EXISTING |
| KITCHEN HAS AN EXISTING STORAGE ROOM. THIS ROUTE CANNOT |
| BE USED AS AN EXIT ACCESS POINT SINCE YOU WOULD BE |
| REQUIRED TO GO THROUGH A STORAGE ROOM. |
| 2020 EXISTING BUILDING CODE LEVEL II 801.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. CREATION OR EXTENSION |
| OF NONCONFORMITY. ALL NEW WORK, RE-CONFIGURATION SHALL |
| NOT CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING |
| BUILDING TO WHICH THE RE-CONFIGURATION OF SPACE IS |
| BEING MADE WITH REGARD TO ACCESSIBILITY, STRUCTURAL |
| STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR THE CAPACITY |
| OF MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS. |
| 2017 FBC-B 1016.2 EGRESS THROUGH INTERVENING SPACES. |
| 1016.2.5. EGRESS SHALL NOT PASS THROUGH KITCHENS, |
| STORAGE ROOMS, CLOSETS OR SPACES USED FOR SIMILAR |
| PURPOSES. |
| |
| 2) SEMI-COMPLIED. LIFE SAFETY PLAN CORRECTED. SHEETS |
| A1, A2, A3, A4, E1, E2, M1 & P1 NOT CORRECTED. |
| DISCREPANCY IN PLANS. |
| PLEASE CORRECT THE LABELING OF KITCHENS AND STORAGE |
| ROOM. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| 1ST ROUND OF COMMENTS. THE LIFE SAFETY PLAN ALSO SHOWS |
| A CODE NON-CONFORMITY IN THE EXISTING KITCHEN, THE |
| ENTRY DOOR INTO THE EXISTING KITCHEN DOES NOT HAVE 18 |
| INCHES MANEUVERING CLEARANCES ON THE LATCH SIDE OF THE |
| DOOR. IN THE 2020 EXISTING BUILDING CODE IN LEVEL 2 |
| ALTERATIONS FOR ACCESSIBILITY ISSUES YOU BACK TO THE |
| 2020 ACCESSIBILITY CODE SECTION 202.4.1. |
| DISPROPORTIONATE COST. FLORIDA ACCESSIBILITY CODE |
| SECTION: DISPROPORTIONATE COST 202.4.1. PLEASE REVIEW |
| HOW YOU ARE TO MEET DISPROPORTIONATE COST. EITHER THE |
| CONTRACTOR OR THE DESIGNER OF RECORD ON THEIR |
| LETTERHEAD NEED TO SHOW HOW THEY ARE GOING TO SPEND UP |
| TO THE 20% DISPROPORTIONATE FUNDS (50,000.00 DOLLARS) |
| LISTED FOR EACH ELEMENT WHERE THE FUNDS ARE BEING SPENT |
| AND IN THE ORDER LISTED IN SECTION 202.4.1 |
| DISPROPORTIONATE COST OF THE 2017 ACCESSIBILITY CODE. |
| |
| 3) COMPLIED. |
| |
| 4) COMPLIED. NOTICE TO THE DESIGNER OF RECORD. |
| |
| 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| 19 |
| |
| IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| 561-718-9724. |
| WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| RETIRED. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| DEVELOPMENT SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| |
| |