Plan Review Notes
Plan Review Notes For Permit 21010015
Permit Number 21010015
Review Stop G
Sequence Number 1
Notes
Date Text
2021-01-11 12:18:53A REVISED GAS RISER HAS BEEN SUBMITTED, REVIEWED AND
 APPROVED BY T.LARGE.
2021-01-08 09:13:261ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21010015
 1/8/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER:
  
 A) PLEASE PROVIDE THE MEASUREMENT OF EACH HORIZONTAL
 SECTION OF PE PIPING, AND EACH CUT SECTION OF
 GALVANIZED PIPING FROM THE PE TRANSITION AT GROUND-
 VERTICALLY TO THE ROOF OF THE BUILDING- AND ACROSS THE
 ROOF OF THE BUILDING TO THE BOILER- SECTION 402.4.1 FBC
 FG.
  
 B) BASED ON THE INDIVIDUAL LOADS SHOWN ON THE RISER,
 CORRECT THE TOTAL BTU LOAD TO INDICATE 1,160,000 BTU-
 SECTION 402.2 FBC FG.
  
 C) LIST THE PIPE SIZING TABLES ON THE PLAN- SECTION
 402.4.1 FBC FG. BASED ON TABLE 402.4(22) THE 1-1/4 PE
 PIPE IS SLIGHTLY UNDERSIZED TO SUPPLY THE TOTAL LOAD.
 THE TABLE INDICATES A MAXIMUM LOAD OF 1020 CFH
 (1,020,000 BTU) FOR 1-1/4 PIPE AT 870 FT TOTAL
 DEVELOPED LENGTH. IT APPEARS A 1-1/2 IN. PE PIPE WILL
 BE REQUIRED.
  
 D) LABEL THE POOL HEATERS AND BOILER AS NEW OR
 EXISTING. PLEASE NOTE THAT THE INSTALL MANUALS FOR THE
 EQUIPMENT SHALL BE ONSITE AT TIME OF INSPECTION TO
 ENSURE PROPER REGULATOR AND GAS PIPING CONNECTIONS PER
 MANUFACTURER'S GUIDELINES- SECTION 301.3, 301.5, &
 305.1 FBC FG.
  
 2) REGULATORS: PLEASE SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE NEW MARKED OR HIGHLIGHTED TO
 SHOW THE SELECTED MAKES AND MODELS, INPUT AND OUTPUT
 PIPE SIZES AND PRESSURES, AND ORIFICE SIZES- SECTION
 410.2 (1) FBC FG.
 A) SHOW ON THE RISER THE REQUIRED PIPE UNIONS FOR THE
 GALVANIZED PIPING WITHIN 1 FT. OF EITHER SIDE OF THE
 REGULATOR.
  
 3) PLEASE PROVIDE A BASIC SITE PLAN DRAWING SHOWING THE
 PIPING RUN FROM THE METER TO THE POOL HEATERS AND TO
 THE BOILER ON THE ROOF. SHOW WHERE THE EXISTING SLEEVES
 ARE ON THE PLAN, SLEEVE LENGTHS, AND THE BURIAL DEPTHS
 OF THE SLEEVES AND THE NEW UNDERGROUND PE- SECTIONS
 404.12 & 404.12.1 FBC FG. INDICATE A YELLOW INSULATED
 COPPER TRACER WIRE OR OTHER APPROVED CONDUCTOR WILL BE
 INSTALLED ADJACENT TO THE UNDERGROUND PE- SECTION
 404.17. 3 FBC FG.
  
 4) PROVIDE PIPING SUPPORT DETAILS FOR THE GALVANIZED
 PIPING RUNNING UP THE BUILDING AND ACROSS THE ROOF
 SURFACE IN ACCORDANCE WITH SECTIONS 404.9 & 407.2 FBC
 FG. PLEASE NOTE THAT PIPE HANGERS AND SUPPORTS SHALL
 CONFORM TO THE REQUIREMENTS OF MSS SP-58 AND SHALL BE
 SPACED IN ACCORDANCE WITH SECTION 415.1 INTERVALS OF
 SUPPORTS.
  
 5) INDICATE HOW THE GALVANIZED PIPING WILL BE PROTECTED
 AGAINST CORROSION FROM MOISTURE- SECTION 404.11 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  