2021-07-06 11:20:46 | 3RD REVIEW FBC-2020 PLUMBING |
| PERMIT- 21010007 |
| 7/6/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESDIENTIAL CODE 7TH EDITION 2020 |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. FOUNDATION REVIEW ONLY- |
| SEPARATE PERMIT REQUIRED FOR NEW CONSTRUCTION OF THE |
| VILLAS. A COMPLETE REVIEW OF THE PLUMBING SYSTEMS WILL |
| NOT BE ACCOMPLISHED AT THIS TIME. PLEASE REVIEW THE |
| COMMENTS BELOW AND RESUBMIT CORRECTED PLANS. |
| |
| 1) 3RD REQUEST FOR CIVIL PLANS. SHEETS P201, P301, |
| P501: REFERENCES ARE MADE FOR CIVIL PLANS THAT ARE |
| SHOWING POINTS OF CONNECTIONS TO WATER, SEWER AND STORM |
| DRAIN MAINS, AND LOCATIONS OF WATER METERS, PREVENTERS |
| ETC.-SECTION 107.2.1 WPB. |
| |
| 2) P201 SANITARY RISERS: VENTS MISSING FOR BATH #2 |
| SHOWERS- SECTION P3101.2.1 FBC P. PLEASE NOTE THAT THIS |
| IS AN ADVISORY COMMENT AND THE ENTIRE PLUMBING SYSTEM |
| IS NOT BEING REVIEWED AT THIS TIME. |
| |
| 5) P101 & P201: SHOW THE WATER HEATER PAN DRAIN LINE |
| RUNS AND DISCHARGE LOCATIONS. PLEASE INDICATE THE TYPE |
| AND SIZE OF PIPES- SECTIONS 504.7.1 AND 504.7.2 FBC P. |
| |
| PLUMBING COMMENTS 4.D & 7 UNDER THE MAIN PERMIT PLANS |
| FOR THE STRUCTURE (21040185) BELOW MUST BE ADDRESSED. |
| ADDITIONAL NOTES IN CAPS PROVIDED. |
| |
| 4.D. ON DETAIL A-2, BEFORE THE METER, YOU HAVE AN NRV. |
| WHAT IS THIS DEVICE, AND WHAT IS THE PURPOSE. PLEASE |
| REMOVE OR CLARIFY PER THE WPB AMENDMENTS TO THE FBC |
| SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| PLEASE NOTE BACKFLOW PREVENTERS FOR THE POTABLE WATER |
| SERVICES ARE REQUIRED AND SHALL BE INSTALLED UNDER |
| SEPARATE PERMITS- SECTION 105.1 WPB. |
| PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR |
| SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE |
| BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB |
| AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL |
| BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS |
| DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. |
| |
| 7. THE PIPES UNDER SLAB NEED TO BE INSULATED WITH A |
| MINIMUM R-3 PER THE 2017 FBC SEC. RE 403.5.3. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |