Plan Review Notes
Plan Review Notes For Permit 21010007
Permit Number 21010007
Review Stop P
Sequence Number 3
Notes
Date Text
2021-07-06 11:20:463RD REVIEW FBC-2020 PLUMBING
 PERMIT- 21010007
 7/6/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESDIENTIAL CODE 7TH EDITION 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FOUNDATION REVIEW ONLY-
 SEPARATE PERMIT REQUIRED FOR NEW CONSTRUCTION OF THE
 VILLAS. A COMPLETE REVIEW OF THE PLUMBING SYSTEMS WILL
 NOT BE ACCOMPLISHED AT THIS TIME. PLEASE REVIEW THE
 COMMENTS BELOW AND RESUBMIT CORRECTED PLANS.
  
 1) 3RD REQUEST FOR CIVIL PLANS. SHEETS P201, P301,
 P501: REFERENCES ARE MADE FOR CIVIL PLANS THAT ARE
 SHOWING POINTS OF CONNECTIONS TO WATER, SEWER AND STORM
 DRAIN MAINS, AND LOCATIONS OF WATER METERS, PREVENTERS
 ETC.-SECTION 107.2.1 WPB.
  
 2) P201 SANITARY RISERS: VENTS MISSING FOR BATH #2
 SHOWERS- SECTION P3101.2.1 FBC P. PLEASE NOTE THAT THIS
 IS AN ADVISORY COMMENT AND THE ENTIRE PLUMBING SYSTEM
 IS NOT BEING REVIEWED AT THIS TIME.
  
 5) P101 & P201: SHOW THE WATER HEATER PAN DRAIN LINE
 RUNS AND DISCHARGE LOCATIONS. PLEASE INDICATE THE TYPE
 AND SIZE OF PIPES- SECTIONS 504.7.1 AND 504.7.2 FBC P.
  
 PLUMBING COMMENTS 4.D & 7 UNDER THE MAIN PERMIT PLANS
 FOR THE STRUCTURE (21040185) BELOW MUST BE ADDRESSED.
 ADDITIONAL NOTES IN CAPS PROVIDED.
  
 4.D. ON DETAIL A-2, BEFORE THE METER, YOU HAVE AN NRV.
 WHAT IS THIS DEVICE, AND WHAT IS THE PURPOSE. PLEASE
 REMOVE OR CLARIFY PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 PLEASE NOTE BACKFLOW PREVENTERS FOR THE POTABLE WATER
 SERVICES ARE REQUIRED AND SHALL BE INSTALLED UNDER
 SEPARATE PERMITS- SECTION 105.1 WPB.
 PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR
 SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE
 BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB
 AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL
 BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 7. THE PIPES UNDER SLAB NEED TO BE INSULATED WITH A
 MINIMUM R-3 PER THE 2017 FBC SEC. RE 403.5.3.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  