2021-05-14 09:23:38 | 2ND REVIEW FBC-2020 PLUMBING |
| PERMIT- 21010007 |
| 5/14/2021 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC RES- FLORIDA RESDIENTIAL CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. FOUNDATION REVIEW ONLY- |
| SEPARATE PERMIT REQUIRED FOR NEW CONSTRUCTION OF THE |
| VILLAS. A COMPLETE REVIEW OF THE PLUMBING SYSTEMS WILL |
| NOT BE ACCOMPLISHED AT THIS TIME. PLEASE REVIEW THE |
| COMMENTS BELOW AND RESUBMIT CORRECTED PLANS. |
| |
| 1) SHEETS P201, P301, P501: REFERENCES ARE MADE FOR |
| CIVIL PLANS THAT ARE SHOWING POINTS OF CONNECTIONS TO |
| WATER, SEWER AND STORM DRAIN MAINS, AND LOCATIONS OF |
| WATER METERS, PREVENTERS ETC. THIS IS THE 2ND REQUEST |
| FOR THE PLANS- SECTION 107.2.1 WPB. |
| 2) PLEASE REVIEW ZONING AND BUILDING COMMENTS REGARDING |
| SITE PLANNING, ADDRESSING AND SEPARATE PERMITTING. A |
| COMPLETE PLUMBING APPROVAL FOR THE VILLA FOUNDATIONS |
| CANNOT BE COMPLETED AT THIS TIME- SECTION 107.2.1 WPB. |
| |
| 3) SHEET P201 SANITARY RISER: THE 3-INCH WASHING |
| MACHINE DRAIN CANNOT CONNECT TO THE FIXTURE DRAIN OF |
| THE WATER CLOSET, AND SHALL CONNECT TO THE BUILDING |
| DRAIN INDEPENDENTLY AT A POINT EITHER DOWNSTREAM OF THE |
| HORIZONTAL WET VENT FOR THE POWDER ROOM- SECTION 912.1 |
| FBC P. |
| |
| 4) P201 SANITARY RISER: THE VENT FOR THE SHOWER IN BATH |
| 2 IS NOT SHOWN- SECTION 910.1 FBC P. PLEASE NOTE THAT |
| THIS IS AN ADVISORY COMMENT AND THE ENTIRE PLUMBING |
| SYSTEM IS NOT BEING REVIEWED AT THIS TIME. |
| |
| 5) P101 & P201: SHOW THE WATER HEATER PAN DRAIN LINE |
| RUNS AND DISCHARGE LOCATIONS. PLEASE INDICATE THE TYPE |
| AND SIZE OF PIPES- SECTIONS 504.7.1 AND 504.7.2 FBC P. |
| |
| 6) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION |
| 105.1 FBC P. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |