2021-07-06 11:19:562ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 21010007
 7/6/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 DENIED,
 THIS IS THE 2ND REVIEW OF THE GAS SYSTEM FOR THE
 FOUNDATION PERMIT. COMMENTS FROM THE IST REVIEW ARE
 LISTED BELOW. THE REQUESTED NARRATIVE RESPONSE TO THE
 1ST REVIEW WAS NOT PROVIDED. ****PLEASE NOTE IF THERE
 WILL BE NO GAS PIPING PENETRATION OF THE NEW FOUNDATION
 SLAB OR RUN BELOW THE FOUNDATION THEN A GAS PIPING
 PERMIT WILL NOT BE REQUIRED FOR THE FOUNDATION ONLY
 PERMIT, AND ALL REVIEW COMMENTS SHALL BE ADDRESSED
 UNDER MASTER PERMIT- 21040185. PLEASE CONTACT ME IF YOU
 NEED FURTHER CLARIFICATION OR ADDITIONAL
 INFORMATION**** SOME COMMENTS HAVE BEEN REMOVED AND
 ADDITIONAL NOTES IN CAPS HAVE BEEN ADDED TO THE 1ST
 REVIEW COMMENTS BELOW.
  
 1ST GAS REVIEW.
 PLAN REVIEW RESULTS: DENIED. FOUNDATION REVIEW ONLY-
 SEPARATE PERMIT REQUIRED FOR NEW CONSTRUCTION OF THE
 VILLAS. A COMPLETE REVIEW OF THE GAS SYSTEM WILL NOT BE
 ACCOMPLISHED AT THIS TIME. BASED ON THE DRAWINGS IT IS
 NOT CLEAR AT THIS TIME IF A GAS PERMIT IS REQUIRED
 UNDER THE FOUNDATION PERMIT, HOWEVER PLEASE REVIEW THE
 COMMENTS BELOW AND PROVIDE A RESPONSE LETTER.
  
 1) SHEETS P401: REFERENCE IS MADE TO CIVIL PLAN SHOWING
 THE POINT OF CONNECTION TO THE METER/TANK. PLEASE
 PROVIDE THE PLAN- SECTION 107.2.1 WPB. NOT PROVIDED
 3) P401: THE GAS PIPING FLOOR PLAN AND THE GAS ISO DO
 NOT MATCH IN TERMS OF WHERE THE GAS PIPING IS MAKING
 PENETRATION INTO THE BUILDING. THE FLOOR PLAN APPEARS
 TO INDICATE THE PIPE COMING UP THROUGH THE FOUNDATION
 AND RUNNING UP THOUGH THE EXTERIOR BLOCK WALL. THE ISO
 APPEARS TO INDICATE A WALL PENETRATION FROM THE
 EXTERIOR TO THE INTERIOR USING A SLEEVE. PLEASE MATCH
 THE TWO DRAWINGS AND REFER TO SECTION 404.14 FBC FG
 PIPING UNDERGROUND BENEATH BUILDINGS. NOT ADDRESSED.
 PIPING INSTALLED UNDERGROUND BENEATH BUILDINGS IS
 PROHIBITED EXCEPT WHERE THE PIPING IS ENCASED IN A
 CONDUIT OF WROUGHT IRON, PLASTIC PIPE, STEEL PIPE, A
 PIPING OR ENCASEMENT SYSTEM LISTED FOR INSTALLATION
 BENEATH BUILDINGS OR OTHER APPROVED CONDUIT MATERIAL
 DESIGNED TO WITHSTAND THE SUPERIMPOSED LOADS. THE
 CONDUIT SHALL BE PROTECTED FROM CORROSION IN ACCORDANCE
 WITH SECTION 404.11 AND SHALL BE INSTALLED IN
 ACCORDANCE WITH SECTION 404.14.1 OR 404.14.2.
 4) P401 GAS ISO: PROVIDE THE TOTAL BTU LOAD OF THE
 SYSTEM- SECTIONS 402.2 & 402.3 FBC FG. NOT PROVIDED.
 5) P401 GAS ISO: THE DRAWING DOES NOT PROPERLY INDICATE
 A RISER PIPE FROM THE UG PE TO THE REGULATOR AND
 SHUTOFF VALVE. PLEASE SEE SECTIONS 404.17.12 AND
 404.17.2 AND INDICATE THE RISER AND TYPE OF TRANSITION
 FITTINGS TO BE INSTALLED. PLEASE NOTE THE CURRENT
 DRAWING APPEARS TO INDICATE THE SHUTOFF VALVE IS
 UNDERGROUND. PLEASE IDENTIFY THE REGULATOR ON THE
 DRAWING. NOT PROVIDED.
 6) P401 GAS ISO: PLEASE IDENTIFY THE REGULATOR ON THE
 DRAWING- SECTION 410.2 FBC FG. NOT PROVIDED.
 7) P401 GAS ISO: REFER TO SECTION 404.8.1 FBC FG AND
 PROVIDE THE TYPE OF SLEEVE AND A VENT FOR THE SLEEVE.
 NOT PROVIDED
 8) P401 GAS ISO- ADVISORY: THE EHD 18 CSST PIPING
 SUPPLY 299 CFH IS UNDERSIZED BASED ON THE SIZING TABLE
 LISTED ON THE DRAWING- TABLE 402.4(16) FBC FG. A
 MINIMUM EHD 30 IS REQUIRED TO SUPPLY THE SYSTEM AND TO
 SUPPLY THE INDIVIDUAL 199 CFH WATER HEATER GAS LOAD.
 NOT PROVIDED.
 9) P401: INDICATE A TRACER WIRE WILL BE INSTALLED FOR
 THE UG PE- SECTION 404.17.3 FBC FG. NOT PROVIDED.
 A YELLOW INSULATED COPPER TRACER WIRE OR OTHER APPROVED
 CONDUCTOR, OR A PRODUCT SPECIFICALLY DESIGNED FOR THAT
 PURPOSE, SHALL BE INSTALLED ADJACENT TO UNDERGROUND
 NONMETALLIC PIPING. ACCESS SHALL BE PROVIDED TO THE
 TRACER WIRE OR THE TRACER WIRE SHALL TERMINATE ABOVE
 GROUND AT EACH END OF THE NONMETALLIC PIPING. THE
 TRACER WIRE SIZE SHALL BE NOT LESS THAN 18 AWG AND THE
 INSULATION TYPE SHALL BE SUITABLE FOR DIRECT BURIAL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  