2021-07-06 11:19:56 | 2ND REVIEW FBC-2020 FUEL GAS |
| PERMIT- 21010007 |
| 7/6/2021 |
| |
| CODES IN EFFECT: |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| DENIED, |
| THIS IS THE 2ND REVIEW OF THE GAS SYSTEM FOR THE |
| FOUNDATION PERMIT. COMMENTS FROM THE IST REVIEW ARE |
| LISTED BELOW. THE REQUESTED NARRATIVE RESPONSE TO THE |
| 1ST REVIEW WAS NOT PROVIDED. ****PLEASE NOTE IF THERE |
| WILL BE NO GAS PIPING PENETRATION OF THE NEW FOUNDATION |
| SLAB OR RUN BELOW THE FOUNDATION THEN A GAS PIPING |
| PERMIT WILL NOT BE REQUIRED FOR THE FOUNDATION ONLY |
| PERMIT, AND ALL REVIEW COMMENTS SHALL BE ADDRESSED |
| UNDER MASTER PERMIT- 21040185. PLEASE CONTACT ME IF YOU |
| NEED FURTHER CLARIFICATION OR ADDITIONAL |
| INFORMATION**** SOME COMMENTS HAVE BEEN REMOVED AND |
| ADDITIONAL NOTES IN CAPS HAVE BEEN ADDED TO THE 1ST |
| REVIEW COMMENTS BELOW. |
| |
| 1ST GAS REVIEW. |
| PLAN REVIEW RESULTS: DENIED. FOUNDATION REVIEW ONLY- |
| SEPARATE PERMIT REQUIRED FOR NEW CONSTRUCTION OF THE |
| VILLAS. A COMPLETE REVIEW OF THE GAS SYSTEM WILL NOT BE |
| ACCOMPLISHED AT THIS TIME. BASED ON THE DRAWINGS IT IS |
| NOT CLEAR AT THIS TIME IF A GAS PERMIT IS REQUIRED |
| UNDER THE FOUNDATION PERMIT, HOWEVER PLEASE REVIEW THE |
| COMMENTS BELOW AND PROVIDE A RESPONSE LETTER. |
| |
| 1) SHEETS P401: REFERENCE IS MADE TO CIVIL PLAN SHOWING |
| THE POINT OF CONNECTION TO THE METER/TANK. PLEASE |
| PROVIDE THE PLAN- SECTION 107.2.1 WPB. NOT PROVIDED |
| 3) P401: THE GAS PIPING FLOOR PLAN AND THE GAS ISO DO |
| NOT MATCH IN TERMS OF WHERE THE GAS PIPING IS MAKING |
| PENETRATION INTO THE BUILDING. THE FLOOR PLAN APPEARS |
| TO INDICATE THE PIPE COMING UP THROUGH THE FOUNDATION |
| AND RUNNING UP THOUGH THE EXTERIOR BLOCK WALL. THE ISO |
| APPEARS TO INDICATE A WALL PENETRATION FROM THE |
| EXTERIOR TO THE INTERIOR USING A SLEEVE. PLEASE MATCH |
| THE TWO DRAWINGS AND REFER TO SECTION 404.14 FBC FG |
| PIPING UNDERGROUND BENEATH BUILDINGS. NOT ADDRESSED. |
| PIPING INSTALLED UNDERGROUND BENEATH BUILDINGS IS |
| PROHIBITED EXCEPT WHERE THE PIPING IS ENCASED IN A |
| CONDUIT OF WROUGHT IRON, PLASTIC PIPE, STEEL PIPE, A |
| PIPING OR ENCASEMENT SYSTEM LISTED FOR INSTALLATION |
| BENEATH BUILDINGS OR OTHER APPROVED CONDUIT MATERIAL |
| DESIGNED TO WITHSTAND THE SUPERIMPOSED LOADS. THE |
| CONDUIT SHALL BE PROTECTED FROM CORROSION IN ACCORDANCE |
| WITH SECTION 404.11 AND SHALL BE INSTALLED IN |
| ACCORDANCE WITH SECTION 404.14.1 OR 404.14.2. |
| 4) P401 GAS ISO: PROVIDE THE TOTAL BTU LOAD OF THE |
| SYSTEM- SECTIONS 402.2 & 402.3 FBC FG. NOT PROVIDED. |
| 5) P401 GAS ISO: THE DRAWING DOES NOT PROPERLY INDICATE |
| A RISER PIPE FROM THE UG PE TO THE REGULATOR AND |
| SHUTOFF VALVE. PLEASE SEE SECTIONS 404.17.12 AND |
| 404.17.2 AND INDICATE THE RISER AND TYPE OF TRANSITION |
| FITTINGS TO BE INSTALLED. PLEASE NOTE THE CURRENT |
| DRAWING APPEARS TO INDICATE THE SHUTOFF VALVE IS |
| UNDERGROUND. PLEASE IDENTIFY THE REGULATOR ON THE |
| DRAWING. NOT PROVIDED. |
| 6) P401 GAS ISO: PLEASE IDENTIFY THE REGULATOR ON THE |
| DRAWING- SECTION 410.2 FBC FG. NOT PROVIDED. |
| 7) P401 GAS ISO: REFER TO SECTION 404.8.1 FBC FG AND |
| PROVIDE THE TYPE OF SLEEVE AND A VENT FOR THE SLEEVE. |
| NOT PROVIDED |
| 8) P401 GAS ISO- ADVISORY: THE EHD 18 CSST PIPING |
| SUPPLY 299 CFH IS UNDERSIZED BASED ON THE SIZING TABLE |
| LISTED ON THE DRAWING- TABLE 402.4(16) FBC FG. A |
| MINIMUM EHD 30 IS REQUIRED TO SUPPLY THE SYSTEM AND TO |
| SUPPLY THE INDIVIDUAL 199 CFH WATER HEATER GAS LOAD. |
| NOT PROVIDED. |
| 9) P401: INDICATE A TRACER WIRE WILL BE INSTALLED FOR |
| THE UG PE- SECTION 404.17.3 FBC FG. NOT PROVIDED. |
| A YELLOW INSULATED COPPER TRACER WIRE OR OTHER APPROVED |
| CONDUCTOR, OR A PRODUCT SPECIFICALLY DESIGNED FOR THAT |
| PURPOSE, SHALL BE INSTALLED ADJACENT TO UNDERGROUND |
| NONMETALLIC PIPING. ACCESS SHALL BE PROVIDED TO THE |
| TRACER WIRE OR THE TRACER WIRE SHALL TERMINATE ABOVE |
| GROUND AT EACH END OF THE NONMETALLIC PIPING. THE |
| TRACER WIRE SIZE SHALL BE NOT LESS THAN 18 AWG AND THE |
| INSULATION TYPE SHALL BE SUITABLE FOR DIRECT BURIAL. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |