Date Text
2021-05-13 16:03:53THE PREVIOUS FIRE COMMENTS WERE NOT SPECIFICALLY
 ADDRESSED.
  
 THE PERMIT WILL BE APPROVED WITH THE PREVIOSU COMMENTS
 AS PROVISO THAT WILL REQUIRE A DETAILED RESPONSE, UNDER
 THE CONSTRUCTION SUBMITTAL OF THE STRUCTURE, TO EACH
 QUESTION ANDD/OR THE APPLICABLE SHEET PAGE THAT
 ADDRESSES THE COMMENT.
  
  
 THE PREVIOUS COMMENTS ARE LIST BELOW:
  
 FIRE HAS NO OBJECTION TO A FOUNDATION PERMIT; THE BELOW
 COMMENTS ARE MORE RELATED TO THE OCCUPANCY
 CLASSIFICATION AND IF A LIFE SAFETY REVIEW IS REQUIRED
 UNDER THE FLORIDA FIRE PREVENTION CODE.
  
 1) SHEET A000 - WITHIN THE SECTION TITLED DESIGN
 PARAMETERS, THERE IS AN INDICATION OF FBC GROUP R-1
 TWO-STORY DUPLEX.
  
 FOR CLARIFICATION PURPOSES, PER THE FLORIDA FIRE
 PREVENTION CODE ARE THESE CONSIDERED A TWO-FAMILY
 DWELLING PER NFPA 101 CH 24....OR ARE THEY ASSOCIATED
 WITH THE PROPOSED HOTEL AND BE RENTED OUT TO CLIENTS
 THUS COMPLYING WITH CH 28.
  
 3.3.145* HOTEL. A BUILDING OR GROUPS OF BUILDINGS UNDER
 THE SAME
 MANAGEMENT IN WHICH THERE ARE SLEEPING ACCOMMODATIONS
 FOR MORE
 THAN 16 PERSONS AND PRIMARILY USED BY TRANSIENTS FOR
 LODGING WITH OR
 WITHOUT MEALS.
  
 28.1.1.5 THE TERM HOTEL, WHEREVER USED IN THIS CODE,
 SHALL INCLUDE
 A HOTEL, AN INN, A CLUB, A MOTEL, A BED AND BREAKFAST,
 OR ANY OTHER
 STRUCTURE MEETING THE DEFINITION OF HOTEL.
  
 PLEASE PROVIDE SPECIFIC DETAILS.
  
  
  
 2) SHOULD THIS BE CLASSIFIED AS AHOTEL OCCUPANCY A FIRE
 SPRINKLER SYTEM IS REQUIRED.
  
 28.3.5 EXTINGUISHMENT REQUIREMENTS.
 28.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY
 AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE
 WITH 28.3.5.3.
  
 PLEASE PROVIDE SPECIFIC DETAILS AND EOR DOCUMENTS PER
 F.A.C. 69G WITH THIS MASTER
  
  
  
 3) SHOULD THIS BE CLASSIFIED AS AHOTEL OCCUPANCY A FIRE
 ALARM SYTEM IS REQUIRED.
  
 28.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 28.3.4.1 GENERAL. A FIRE ALARM SYSTEM IN ACCORDANCE
 WITH SECTION
 9.6, EXCEPT AS MODIFIED BY 28.3.4.2 THROUGH 28.3.4.6,
 SHALL BE
 PROVIDED.
  
 PLEASE PROVIDE SPECIFIC DETAILS WITH THIS MASTER.
  
  
 4) SHOULD THIS BE CLASSIFIED AS A HOTEL OCCUPANCY AND
 WITH AN ATTACHED GARAGE
  
 28.3.4.6 CARBON MONOXIDE ALARMS AND CARBON MONOXIDE
 DETECTION SYSTEMS.
 28.3.4.6.1 CARBON MONOXIDE ALARMS OR CARBON MONOXIDE
 DETECTORS
 IN ACCORDANCE WITH SECTION 9.8 AND 28.3.4.6 SHALL BE
 PROVIDED IN
 NEW HOTELS AND DORMITORIES WHERE EITHER OF THE
 FOLLOWING
 CONDITIONS EXISTS:
 (1) GUEST ROOMS OR GUEST SUITES WITH COMMUNICATING
 ATTACHED
 GARAGES, UNLESS OTHERWISE EXEMPTED BY 28.3.4.6.3
 (2) GUEST ROOMS OR GUEST SUITES CONTAINING A
 PERMANENTLY
 INSTALLED FUEL-BURNING APPLIANCE OR FUEL-BURNING
 FIREPLACE
  
 PLEASE PROVIDE SPECIFIC DETAILS WITH THIS MASTER.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  