Plan Review Notes For Permit 21010007 |
Permit Number |
21010007 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-01-22 13:47:39 | 1ST REVIEW FBC-2020 PLUMBING | | PERMIT- 21010007 | | 1/22/2021 | | | | CODES IN EFFECT: | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FBC RES- FLORIDA RESDIENTIAL CODE 7TH EDITION 2020 | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | 2020 | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE PROVIDE PLUMBING RISER DRAWINGS AND A GROUND | | FLOOR PIPING PLAN SHOWING ALL UNDER SLAB PIPING- | | SANITARY, WATER SERVICE AND DISTRIBUTION, GAS, | | CONDENSATE, AND STORM- SECTIONS 107.2.1 & 107.3.5.1.3 | | WPB. PLEASE INCLUDE A CIVIL PLAN SHOWING POINTS OF | | CONNECTION TO ONSITE MAIN UTILITY PIPING. | | | | 2) SHEET A000: PLEASE UPDATE THE CODE EDITION TO THE | | FLORIDA BUILDING CODE- 2020 7TH EDITION WHICH WENT INTO | | EFFECT ON 12/31/2020. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|