Plan Review Notes
Plan Review Notes For Permit 20121415
Permit Number 20121415
Review Stop B
Sequence Number 3
Notes
Date Text
2021-03-09 12:07:1303/09/21
 EMAILED JASON MOAN. WAITING ON HEATER SPECS TO FINISH
 REVIEW. PLANS NEED TO REFLECT HEATER SPECS.
  
  
  
 03/03/21
 NOTE: COURTESY REVIEW OF PLAN EMAILED BY JASON MOAN.
  
 1) 53"X37" SINGLE HUNG WINDOW DOESN'T COMPLY WITH THE
 EMERGENCY ESCAPE REQUIREMENTS.
 2) CARBON MONOXIDE ALARMS INFORMATION IS NOT CLEAR.
 LEGEND BELOW THE FLOOR PLANS SHOW SMOKE DETECTOR
 SYMBOL. IT IS NOT CLEAR IF THIS IS AN SMOKER DETECTOR
 AND CARBON MONOXIDE ALARM COMBO. AND, THERE IS A NOTE
 STATING "CARBON WITHIN 12' OF BEDROOMS". NOT CLEAR
 ABOUT THIS NOTE. IS IT GOING TO BE CARBON MONOXIDE
 ALARM INSIDE AND OUTSIDE THE BEDROOMS AS SHOWN ON
 PLANS?. ALSO, ACCORDING TO SEC. R315.1 FBC-RESIDENTIAL
 CARBON MONOXIDE ALARMS NEED TO BE AT LEAST 10 FEET FROM
 EACH BEDROOM NOT 12 FEET. REVISE AS REQUIRED.
  
 3) NOTE: NEED TO PROVIDE INFORMATION ABOUT THE HEAT
 SOURCE FOR NEW BEDROOM #3 AND ROOM FACING THE BEDROOM.
 THIS WAS REQUESTED BY THE MECHANICAL PLANS EXAMINER. I
 DIDN'T SEE ANY INFORMATION SHOWING COMPLIANCE WITH THIS
 REQUIREMENT. IF USING WINDOW UNITS, THEN NEED DEDICATED
 OUTLETS (220 OUTLET MAY BE REQUIRED). SEC. R303.10
 FBC-RESIDENTIAL.
  
  
  
 ORIGINAL COMMENTS BELOW:
  
  
  
 RESIDENTIAL (R3)ALTERATION TO COVERT BACK HOUSE TO ONE
 SINGLE FAMILY RESIDENCE: BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 PERMIT #20121415
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
 1- DRAWING 1 OF 1 NEEDS TO HAVE THE SEAL AND SIGNATURE
 OF THE ENGINEER OF RECORD (THOMAS J. TWOMEY, P.E.).
 NEED ORIGINAL SEAL/SIGNATURE AS REQUIRED BY SEC.
 61G15-23.001 FAC AND CHAPTER 471 F.S. WHEN SUBMITTING
 PLANS/DOCUMENTS FOR PUBLIC RECORDS.
  
 2- ACCORDING TO CITY RECORDS, NEW BEDROOM #3 IS LOCATED
 WHERE THE PORCH USED TO BE. THERE ARE NO CITY RECORDS
 SHOWING PORCH ALTERATIONS. NEED TO SPECIFY SIZE AND
 TYPE OF WINDOWS TO VERIFY COMPLIANCE WITH TH EGRESS
 REQUIREMENTS OF SEC. R310.2.1 FBC-RESIDENTIAL. AT LEAST
 ONE WINDOW NEEDS TO COMPLY WITH THE EGRESS
 REQUIREMENTS.
 SEC. 504 FBC-EXISTING BUILDING. SEC. 801.3 FBC-EXISTING
 BUILDING.
  
 3- SHOW ON THE FLOOR PLAN THE LOCATION OF CARBON
 MONOXIDE ALARMS FOR ALL BEDROOMS, INCLUDING EXISTING
 BEDROOMS AS REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL.
 SEC. 504 FBC-EXISTING BUILDING. SEC. 801.3 FBC-EXISTING
 BUILDING.
  
 4- SHOW ON THE FLOOR PLAN THE LOCATION OF SMOKE ALARMS
 FOR ALL ALL BEDROOMS, INCLUDING EXISTING BEDROOMS AS
 REQUIRED BY SEC. R314 FBC-RESIDENTIAL.
 SEC. 504 FBC-EXISTING BUILDING. SEC. 801.3 FBC-EXISTING
 BUILDING.
  
 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW.
 VALUATION IS FOR ALL WORK SHOWN ON PLANS THAT WAS DONE
 WITHOUT PERMITS. VALUATION TO INCLUDE ALL LABOR,
 MATERIALS, CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. UPDATE VALUATION AS REQUIRED, INCLUDING
 DESIGN PROFESSIONAL FEES.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  