2021-03-09 12:07:13 | 03/09/21 |
| EMAILED JASON MOAN. WAITING ON HEATER SPECS TO FINISH |
| REVIEW. PLANS NEED TO REFLECT HEATER SPECS. |
| |
| |
| |
| 03/03/21 |
| NOTE: COURTESY REVIEW OF PLAN EMAILED BY JASON MOAN. |
| |
| 1) 53"X37" SINGLE HUNG WINDOW DOESN'T COMPLY WITH THE |
| EMERGENCY ESCAPE REQUIREMENTS. |
| 2) CARBON MONOXIDE ALARMS INFORMATION IS NOT CLEAR. |
| LEGEND BELOW THE FLOOR PLANS SHOW SMOKE DETECTOR |
| SYMBOL. IT IS NOT CLEAR IF THIS IS AN SMOKER DETECTOR |
| AND CARBON MONOXIDE ALARM COMBO. AND, THERE IS A NOTE |
| STATING "CARBON WITHIN 12' OF BEDROOMS". NOT CLEAR |
| ABOUT THIS NOTE. IS IT GOING TO BE CARBON MONOXIDE |
| ALARM INSIDE AND OUTSIDE THE BEDROOMS AS SHOWN ON |
| PLANS?. ALSO, ACCORDING TO SEC. R315.1 FBC-RESIDENTIAL |
| CARBON MONOXIDE ALARMS NEED TO BE AT LEAST 10 FEET FROM |
| EACH BEDROOM NOT 12 FEET. REVISE AS REQUIRED. |
| |
| 3) NOTE: NEED TO PROVIDE INFORMATION ABOUT THE HEAT |
| SOURCE FOR NEW BEDROOM #3 AND ROOM FACING THE BEDROOM. |
| THIS WAS REQUESTED BY THE MECHANICAL PLANS EXAMINER. I |
| DIDN'T SEE ANY INFORMATION SHOWING COMPLIANCE WITH THIS |
| REQUIREMENT. IF USING WINDOW UNITS, THEN NEED DEDICATED |
| OUTLETS (220 OUTLET MAY BE REQUIRED). SEC. R303.10 |
| FBC-RESIDENTIAL. |
| |
| |
| |
| ORIGINAL COMMENTS BELOW: |
| |
| |
| |
| RESIDENTIAL (R3)ALTERATION TO COVERT BACK HOUSE TO ONE |
| SINGLE FAMILY RESIDENCE: BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| PERMIT #20121415 |
| |
| NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE. |
| |
| 1- DRAWING 1 OF 1 NEEDS TO HAVE THE SEAL AND SIGNATURE |
| OF THE ENGINEER OF RECORD (THOMAS J. TWOMEY, P.E.). |
| NEED ORIGINAL SEAL/SIGNATURE AS REQUIRED BY SEC. |
| 61G15-23.001 FAC AND CHAPTER 471 F.S. WHEN SUBMITTING |
| PLANS/DOCUMENTS FOR PUBLIC RECORDS. |
| |
| 2- ACCORDING TO CITY RECORDS, NEW BEDROOM #3 IS LOCATED |
| WHERE THE PORCH USED TO BE. THERE ARE NO CITY RECORDS |
| SHOWING PORCH ALTERATIONS. NEED TO SPECIFY SIZE AND |
| TYPE OF WINDOWS TO VERIFY COMPLIANCE WITH TH EGRESS |
| REQUIREMENTS OF SEC. R310.2.1 FBC-RESIDENTIAL. AT LEAST |
| ONE WINDOW NEEDS TO COMPLY WITH THE EGRESS |
| REQUIREMENTS. |
| SEC. 504 FBC-EXISTING BUILDING. SEC. 801.3 FBC-EXISTING |
| BUILDING. |
| |
| 3- SHOW ON THE FLOOR PLAN THE LOCATION OF CARBON |
| MONOXIDE ALARMS FOR ALL BEDROOMS, INCLUDING EXISTING |
| BEDROOMS AS REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL. |
| SEC. 504 FBC-EXISTING BUILDING. SEC. 801.3 FBC-EXISTING |
| BUILDING. |
| |
| 4- SHOW ON THE FLOOR PLAN THE LOCATION OF SMOKE ALARMS |
| FOR ALL ALL BEDROOMS, INCLUDING EXISTING BEDROOMS AS |
| REQUIRED BY SEC. R314 FBC-RESIDENTIAL. |
| SEC. 504 FBC-EXISTING BUILDING. SEC. 801.3 FBC-EXISTING |
| BUILDING. |
| |
| 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW. |
| VALUATION IS FOR ALL WORK SHOWN ON PLANS THAT WAS DONE |
| WITHOUT PERMITS. VALUATION TO INCLUDE ALL LABOR, |
| MATERIALS, CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN |
| PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| AMENDMENTS. UPDATE VALUATION AS REQUIRED, INCLUDING |
| DESIGN PROFESSIONAL FEES. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |