Date |
Text |
2021-01-06 14:55:03 | REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. THE CITY OF WEST PALM BEACH HAS NO RECORD OF A GAS |
| PERMIT FOR THE HEATER OUTSIDE. THIS IS UP TO THE |
| HOMEOWNER TO MAKE AN APPLICATION TO THE BUILDING |
| OFFICIAL AND OBTAIN THE REQUIRED PERMIT PER THE WPB |
| AMENDMENTS TO THE FBC SEC. 105.1. |
| |
| 2. TANK TYPE WATER HEATERS ARE NOT MADE FOR OUTDOOR USE |
| PER THE MANUFACTURERS SPECIFICATION UNLESS IN AN |
| APPROVED STRUCTURE SUPPORTED BY THE MANUFACTURER. |
| PLEASE PROVIDE MANUFACTURES SPECIFICATIONS FOR THE UNIT |
| PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 3. A SUB GAS PERMIT IS REQUIRED BY A LICENSED |
| CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 105.1. |
| |
| 4. PLEASE SUBMIT A GAS RISER ISOMETRIC DRAWING PER THE |
| WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) |
| RESIDENTIAL GAS. |
| |
| 5. SUBMIT ON THE ISOMETRIC DRAWING THE LENGTH OF ALL |
| CUT SECTIONS OF PIPE PER 2017 FBC RES. SECS. G2413.4.1, |
| G2413.4.2. |
| |
| 6. TYPE OF GAS (LP OR NATURAL) PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| 7. IS THIS THE ONLY GAS APPLIANCE AND THE TOTAL BTU |
| LOAD ON THE SYSTEM? REFER TO THE 2017 FBC RES. SEC. |
| G2413. |
| |
| 8. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN PER THE 2017 FBC RES. SEC. G2413.2. |
| |
| 9. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE, |
| TERMINATION POINT, HEIGHT ABOVE THE ROOF, AND ANCHORING |
| ELEMENTS OF THE GAS VENT(S) PER THE 2017 FBC RES. SECS. |
| G2426 THRU G2429.1. |
| |
| 10. THE GAS HEATER SHALL BE LISTED AND LABELED. THE |
| INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2017 |
| FBC RES. SEC. G2413.2 AND G2404.3. |
| |
| 11. SUBMIT A COPY OF THE SIZING TABLE USED IN THE |
| DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE PLAN LISTING |
| THE SIZING TABLES FROM GAS CODES OR ANOTHER STANDARD |
| USED IN THIS SYSTEM'S DESIGN PER THE 2017 FBC FG. 402.3 |
| OR 2017 FBC RES. SEC. G2413.3. |
| |
| 12. PLEASE SHOW THE DISTANCE FROM THE TWO PSI REGULATOR |
| TO THE APPLIANCE. COMPLY WITH 2017 FBC FG RES. TABLE |
| G2413.4 (12) FOR THE PROPER PIPE SIZE AND BTU LOAD. |
| |
| 13. GAS APPLIANCES (WATER HEATER) SHALL NOT BE |
| PROHIBITED UNLESS IT COMPLIES WITH PER THE 2017 FBC |
| RES. SEC. G2406.2. |
| |
| 14. SIGNATURE (OR SEAL, OR TITLE BLOCK, OR ALL THREE) |
| ARE NOT IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE |
| 61G15-23.001, FLORIDA STATUTE 471 PER THE WPB |
| AMENDMENTS TO THE FBC SEC. 107.1 GENERAL. |
| |
| 15. HOW IS THIS GAS VENTED AND IT IT NEAR A WINDOW, |
| PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC. |
| 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |