Plan Review Notes
Plan Review Notes For Permit 20121415
Permit Number 20121415
Review Stop G
Sequence Number 1
Notes
Date Text
2021-01-06 14:55:03REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE CITY OF WEST PALM BEACH HAS NO RECORD OF A GAS
 PERMIT FOR THE HEATER OUTSIDE. THIS IS UP TO THE
 HOMEOWNER TO MAKE AN APPLICATION TO THE BUILDING
 OFFICIAL AND OBTAIN THE REQUIRED PERMIT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 105.1.
  
 2. TANK TYPE WATER HEATERS ARE NOT MADE FOR OUTDOOR USE
 PER THE MANUFACTURERS SPECIFICATION UNLESS IN AN
 APPROVED STRUCTURE SUPPORTED BY THE MANUFACTURER.
 PLEASE PROVIDE MANUFACTURES SPECIFICATIONS FOR THE UNIT
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 4. PLEASE SUBMIT A GAS RISER ISOMETRIC DRAWING PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12)
 RESIDENTIAL GAS.
  
 5. SUBMIT ON THE ISOMETRIC DRAWING THE LENGTH OF ALL
 CUT SECTIONS OF PIPE PER 2017 FBC RES. SECS. G2413.4.1,
 G2413.4.2.
  
 6. TYPE OF GAS (LP OR NATURAL) PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 7. IS THIS THE ONLY GAS APPLIANCE AND THE TOTAL BTU
 LOAD ON THE SYSTEM? REFER TO THE 2017 FBC RES. SEC.
 G2413.
  
 8. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER THE 2017 FBC RES. SEC. G2413.2.
  
 9. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE,
 TERMINATION POINT, HEIGHT ABOVE THE ROOF, AND ANCHORING
 ELEMENTS OF THE GAS VENT(S) PER THE 2017 FBC RES. SECS.
 G2426 THRU G2429.1.
  
 10. THE GAS HEATER SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2017
 FBC RES. SEC. G2413.2 AND G2404.3.
  
 11. SUBMIT A COPY OF THE SIZING TABLE USED IN THE
 DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE PLAN LISTING
 THE SIZING TABLES FROM GAS CODES OR ANOTHER STANDARD
 USED IN THIS SYSTEM'S DESIGN PER THE 2017 FBC FG. 402.3
 OR 2017 FBC RES. SEC. G2413.3.
  
 12. PLEASE SHOW THE DISTANCE FROM THE TWO PSI REGULATOR
 TO THE APPLIANCE. COMPLY WITH 2017 FBC FG RES. TABLE
 G2413.4 (12) FOR THE PROPER PIPE SIZE AND BTU LOAD.
  
 13. GAS APPLIANCES (WATER HEATER) SHALL NOT BE
 PROHIBITED UNLESS IT COMPLIES WITH PER THE 2017 FBC
 RES. SEC. G2406.2.
  
 14. SIGNATURE (OR SEAL, OR TITLE BLOCK, OR ALL THREE)
 ARE NOT IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE
 61G15-23.001, FLORIDA STATUTE 471 PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.1 GENERAL.
  
 15. HOW IS THIS GAS VENTED AND IT IT NEAR A WINDOW,
 PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  