2021-01-06 16:41:00 | PLAN REVIEW / ELECTRICAL |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER BUILDING - PX3169 |
| PLANS EXAMINER 1&2 FAMILY - SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| 2014 NEC |
| 2017 FBC EXISTING BUILDING ALTERATION LEVEL 2 |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| NOTICE: ALL NEW ELECTRICAL SYSTEMS AND DEVICES SHALL BE |
| BROUGHT UP TO CURRENT CODE REQUIREMENTS. |
| |
| |
| 1. SMOKE ALARMS SHALL BE LOCATED AS REQUIRED FOR NEW |
| DWELLINGS PER R314.2.2 |
| |
| R314.2.2ALTERATIONS, REPAIRS AND ADDITIONS. |
| WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE |
| ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| |
| 2. CARBON MONOXIDE DETECTORS SHALL BE LOCATED PER |
| R315.1 SEE DESIGNERS NOTE ON PLAN PAGE 1 OF 1. |
| |
| R315.1 CARBON MONOXIDE PROTECTION. |
| EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING |
| BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS |
| ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR |
| APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER |
| FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE |
| AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL |
| CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH |
| ROOM USED FOR SLEEPING PURPOSES. |
| |
| |
| WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |
| |
| |
| |