Plan Review Notes
Plan Review Notes For Permit 20121402
Permit Number 20121402
Review Stop G
Sequence Number 1
Notes
Date Text
2021-01-06 17:12:4801/06/20 2ND GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE SHOW ON GAS ISOMETRIC DRAWING THE LENGTH OF
 ALL CUT SECTIONS OF PIPE PER 2017 FBC RES. SECS.
 G2413.4.1, G2413.4.2.
  
 2. PLEASE SHOW WHAT TYPE OF GAS (LP OR NATURAL) PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 3. PLEASE SUBMIT CALCULATIONS FOR COMBUSTION AIR PER
 THE 2017 FBC FG SEC. 304.1, 614.5 (CLOTHES DRYERS), OR
 2017 FBC RES. SEC. G2407.1 AND G2439.4 (CLOTHES
 DRYERS).
  
 4. IF USING LOUVER FOR COMBUSTION AIR, PLEASE SHOW THE
 SIZE OF THE LOUVER(S) ON THE PLANS PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 5. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE ISOMETRIC PER THE 2017 FBC RES. SEC. G2413.2.
  
 6. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE,
 TERMINATION POINT, HEIGHT ABOVE THE ROOF, AND ANCHORING
 DETAILS OF THE GAS VENT(S) PER THE 2017 FBC FG SECS.
 502 THRU 505 OR 2017 FBC RES. SECS. G2426 THRU G2429.1.
  
 7. PLEASE PROVIDE MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2017 FBC RES. SEC. G2408.1.
  
 8. PLEASE SUBMIT THE MANUFACTURER?S SPECIFICATIONS FOR
 THE PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 BUILDING'S EXTERIOR SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2017 FBC FG SEC. 410.1 OR 2017 FBC
 RES. SEC. G2421.1.
  
 9. PLEASE SHOW AND LABEL ALL SHUTOFF VALVES ON GAS
 ISOMERIC PER THE 2017 FBC RES. SEC. G2401.1.3, SHUTOFF
 VALVE FOR EACH APPLIANCE SHALL BE ACCESSIBLE WITHOUT
 MOVING THE APPLIANCE.
  
 10. PLEASE SHOW THE TANK-LESS WATER HEATER'S LOCATION
 AND THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR
 WINDOWS IN RELATION TO THE WATER HEATER. THE WATER
 HEATER'S LOCATION SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  