2021-01-27 09:04:11 | PLAN REVIEW / ELECTRICAL |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER BUILDING - PX3169 |
| PLANS EXAMINER 1&2 FAMILY - SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| 2014 NEC |
| |
| NOTICE TO APPLICANT: |
| |
| THE CITY REQUIRES A SEPERATE PERMIT FOR EACH STRUCTURE |
| SITUATED ON A SINGLE LOT. SUBMIT A PERMIT APPLICATION |
| FOR THE CABANA. |
| BOTH STRUCTURES MAY REMAIN ON ONE SET OF PLANS. PERMITS |
| WILL TRAVEL TOGETHER. |
| VALUE OF THE CABANA HAS BEEN CALCULATED TO BE |
| $36,478.00 PER THE ICC BUILDING VALUATION TABLES, |
| CONSTRUCTION TYPE IIIB. |
| |
| 1ST REVIEW - MAIN DWELLING UNIT. |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. PROVIDE ACTUAL TRANSFORMER SECONDARY FAULT CURRENT |
| FROM UTILITY. |
| |
| AIC RATING OF SERVICE DISCONNECT AND PANEL |
| |
| PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| NEC 110.9, 110.10; FBC RE E3404.2 & FBC RE E3606.3 |
| |
| FBC R E3606.3AVAILABLE SHORT-CIRCUIT CURRENT. |
| SERVICE EQUIPMENT SHALL BE SUITABLE FOR THE MAXIMUM |
| FAULT CURRENT AVAILABLE AT ITS SUPPLY TERMINALS, BUT |
| NOT LESS THAN 10,000 AMPERES. (110.9) |
| E3706.1PANELBOARD RATING. |
| ALL PANELBOARDS SHALL HAVE A RATING NOT LESS THAN THAT |
| OF THE MINIMUM SERVICE OR FEEDER CAPACITY REQUIRED FOR |
| THE CALCULATED LOAD. (408.30) |
| |
| 2. PLAN PAGE E101 STATES THE MEP EQUIPMENT SHALL BE |
| LOCATED ABOVE THE BASE FLOOD ELEVATION (BFE). THIS |
| PROPERTY IS NOT LOCATED IN A SPECIAL FLOOD HAZARD AREA |
| (SFHA) AND DOES NOR HAVE A BFE. |
| PLAN PAGE A101 STATES FINISHED FLOOR ELEVATION SHALL BE |
| 18.0' NAVD (18" MIN. ABOVE CROWN OF ROADWAY). |
| SEE FINISHED FLOOR ELEVATION COMMENT UNDER BUILDING |
| REVIEW. |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| |
| |
| |
| 1ST REVIEW - CABANA (THESE COMMENTS WILL BE TRANSFERED |
| TO CABANA PERMIT WHEN ISSUED) |
| |
| 1. PROVIDE EXIT DOOR ILLUMINATION. |
| FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED |
| GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL |
| SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON |
| THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE |
| LEVEL ACCESS. PROVIDE CORRECTION. NEC 210.70(A)(2)(B), |
| FBC RE E3903.3 |
| |
| 2. PANEL P REQUIRES MEANS OF DISCONNECT. |
| |
| A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A |
| BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE |
| DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE |
| FEEDER OR BRANCH CIRCUIT. NEC 225.30 |
| |
| PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A |
| BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH |
| CIRCUIT. NEC 250.32; FBC RE3607.3 |
| |
| FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A |
| DISCONNECTING MEANS AT THE BUILDING OR SEPARATE |
| STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR |
| MAIN BREAKER AT THE PANEL FOR PANEL A. NEC 225.31, |
| 225.32 |
| E3601.6SERVICE DISCONNECT REQUIRED. |
| MEANS SHALL BE PROVIDED TO DISCONNECT ALL CONDUCTORS IN |
| A BUILDING OR OTHER STRUCTURE FROM THE SERVICE ENTRANCE |
| CONDUCTORS. (230.70) |
| |
| 3. PANEL P WORKING CLEARANCE. (POOL EQUIPMENT) |
| E3405.1WORKING SPACE AND CLEARANCES. |
| ACCESS AND WORKING SPACE SHALL BE PROVIDED AND |
| MAINTAINED AROUND ALL ELECTRICAL EQUIPMENT TO PERMIT |
| READY AND SAFE OPERATION AND MAINTENANCE OF SUCH |
| EQUIPMENT IN ACCORDANCE WITH THIS SECTION AND FIGURE |
| E3405.1. (110.26) |
| |
| |
| |
| |
| |
| |
| |