Plan Review Notes
Plan Review Notes For Permit 20121402
Permit Number 20121402
Review Stop E
Sequence Number 1
Notes
Date Text
2021-01-27 09:04:11PLAN REVIEW / ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 NOTICE TO APPLICANT:
  
 THE CITY REQUIRES A SEPERATE PERMIT FOR EACH STRUCTURE
 SITUATED ON A SINGLE LOT. SUBMIT A PERMIT APPLICATION
 FOR THE CABANA.
 BOTH STRUCTURES MAY REMAIN ON ONE SET OF PLANS. PERMITS
 WILL TRAVEL TOGETHER.
 VALUE OF THE CABANA HAS BEEN CALCULATED TO BE
 $36,478.00 PER THE ICC BUILDING VALUATION TABLES,
 CONSTRUCTION TYPE IIIB.
  
 1ST REVIEW - MAIN DWELLING UNIT.
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE ACTUAL TRANSFORMER SECONDARY FAULT CURRENT
 FROM UTILITY.
  
 AIC RATING OF SERVICE DISCONNECT AND PANEL
  
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3404.2 & FBC RE E3606.3
  
 FBC R E3606.3AVAILABLE SHORT-CIRCUIT CURRENT.
 SERVICE EQUIPMENT SHALL BE SUITABLE FOR THE MAXIMUM
 FAULT CURRENT AVAILABLE AT ITS SUPPLY TERMINALS, BUT
 NOT LESS THAN 10,000 AMPERES. (110.9)
 E3706.1PANELBOARD RATING.
 ALL PANELBOARDS SHALL HAVE A RATING NOT LESS THAN THAT
 OF THE MINIMUM SERVICE OR FEEDER CAPACITY REQUIRED FOR
 THE CALCULATED LOAD. (408.30)
  
 2. PLAN PAGE E101 STATES THE MEP EQUIPMENT SHALL BE
 LOCATED ABOVE THE BASE FLOOD ELEVATION (BFE). THIS
 PROPERTY IS NOT LOCATED IN A SPECIAL FLOOD HAZARD AREA
 (SFHA) AND DOES NOR HAVE A BFE.
 PLAN PAGE A101 STATES FINISHED FLOOR ELEVATION SHALL BE
 18.0' NAVD (18" MIN. ABOVE CROWN OF ROADWAY).
 SEE FINISHED FLOOR ELEVATION COMMENT UNDER BUILDING
 REVIEW.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
  
  
 1ST REVIEW - CABANA (THESE COMMENTS WILL BE TRANSFERED
 TO CABANA PERMIT WHEN ISSUED)
  
 1. PROVIDE EXIT DOOR ILLUMINATION.
 FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED
 GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL
 SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON
 THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE
 LEVEL ACCESS. PROVIDE CORRECTION. NEC 210.70(A)(2)(B),
 FBC RE E3903.3
  
 2. PANEL P REQUIRES MEANS OF DISCONNECT.
  
 A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A
 BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE
 DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE
 FEEDER OR BRANCH CIRCUIT. NEC 225.30
  
 PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A
 BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH
 CIRCUIT. NEC 250.32; FBC RE3607.3
  
 FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR PANEL A. NEC 225.31,
 225.32
 E3601.6SERVICE DISCONNECT REQUIRED.
 MEANS SHALL BE PROVIDED TO DISCONNECT ALL CONDUCTORS IN
 A BUILDING OR OTHER STRUCTURE FROM THE SERVICE ENTRANCE
 CONDUCTORS. (230.70)
  
 3. PANEL P WORKING CLEARANCE. (POOL EQUIPMENT)
 E3405.1WORKING SPACE AND CLEARANCES.
 ACCESS AND WORKING SPACE SHALL BE PROVIDED AND
 MAINTAINED AROUND ALL ELECTRICAL EQUIPMENT TO PERMIT
 READY AND SAFE OPERATION AND MAINTENANCE OF SUCH
 EQUIPMENT IN ACCORDANCE WITH THIS SECTION AND FIGURE
 E3405.1. (110.26)
  
  
  
  
  
  
  