Plan Review Notes
Plan Review Notes For Permit 20121397
Permit Number 20121397
Review Stop P
Sequence Number 1
Notes
Date Text
2021-01-12 17:01:03CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20121397 730 BELVEDERE RD
  
 1ST REVIEW
 PLUMBING COMMENTS:
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.VALUE OF JOB SEEMS LOW WHEN COMPARED TO ENTIRE SCOPE
 OF WORK. PROVIDE AN ACCURATE VALUATION OF ALL WORK AND
 COST. 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE
 OPINION OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION
 OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL (1)CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 CHAPTERS 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS FOR
 NEW TOILET ROOM INDICATING THE FOLLOWING:
 A.THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18
 INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC
 ACC 604.2
 B.CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND
 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL PER FBC ACC 604.3.1
 C.THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL PER FBC ACC 604.5.1
 D.THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 E.FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC.
 HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309.
 FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE
 WATER CLOSET PER FBC ACC 604.6
 F.TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC
 ACC 604.8.
 G.THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER
 FBC ACC 604.4.
 H.LAVATORIES AND ACCESSIBLE SINKS SHALL BE INSTALLED
 WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER
 SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND PER FBC ACC 606.3, ADDITIONALLY SHOW TOE AND
 KNEE CLEARANCE AS REQUIRED BY FBC ACC 306.2 AND 306.3
 I.PER FBC 606.5 EXPOSED PIPES AND SURFACES. WATER
 SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT.
 J.UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2
 K.MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND PER FBC ACC 603.3.
 L.DRINKING FOUNTAINS SHALL COMPLY WITH 307 AND 602 PER
 FBC ACC 602.1.
 M.REFERENCE THE DRINKING FOUNTAIN: PROTRUDING OBJECTS
 307.2 PROTRUSION LIMITS 307.2. OBJECTS WITH LEADING
 EDGES MORE THAN 27 INCHES AND NOT MORE THAN 80 INCHES
 ABOVE THE FLOOR SHALL NOT PROTRUDE MORE THAN 4 INCHES
 HORIZONTALLY INTO THE CIRCULATION PATH.
 N.602.2CLEAR FLOORUNITS SHALL HAVE A CLEAR FLOOR OR
 GROUND SPACE COMPLYING WITH 305 POSITIONED FOR A
 FORWARD APPROACH AND CENTERED ON THE UNIT. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED PER FBC
 ACC 602.2.
 O.OPERABLE PARTS SHALL COMPLY WITH 309 PER FBC ACC
 602.3.
 P.SPOUT OUTLETS SHALL BE 36 INCHES (915 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND PER FBC ACC 602.4.
 Q.SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING
 PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43
 INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND PER FBC ACC 602.7
 R.THE SPOUT SHALL BE LOCATED 15 INCHES (380 MM) MINIMUM
 FROM THE VERTICAL SUPPORT AND 5 INCHES (125 MM) MAXIMUM
 FROM THE FRONT EDGE OF THE UNIT, INCLUDING BUMPERS PER
 FBC ACC 602.5.
 S.PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP (NOT
 THE CENTER) OF THE GRIPPING SURFACE,
  
 3.PER FBC PL 403.3.1, THE ROUTE TO THE PUBLIC TOILET
 FACILITIES REQUIRED BY SECTION 403.3 SHALL NOT PASS
 THROUGH KITCHENS (FOOD PREP AREAS), STORAGE ROOMS OR
 CLOSETS. ACCESS TO THE REQUIRED FACILITIES SHALL BE
 FROM WITHIN THE BUILDING OR FROM THE EXTERIOR OF THE
 BUILDING. ROUTES SHALL COMPLY WITH THE ACCESSIBILITY
 REQUIREMENTS OF THE FLORIDA BUILDING CODE,
 ACCESSIBILITY. THE PUBLIC SHALL HAVE ACCESS TO THE
 REQUIRED TOILET FACILITIES AT ALL TIMES THAT THE
 BUILDING IS OCCUPIED.
  
 4.PER FBC PL 608.1 AND WPB CCCM A BACKFLOW PREVENTER IS
 REQUIRED FOR THE POTABLE WATER SERVICE AND SHALL BE
 INSTALLED TO COMPLY WITH THE WPB CCCM REQUIREMENTS AND
 SHALL BE LEAD FREE. PER WPB FBC 107.2.1, PROVIDE
 SPECIFICATION FOR SAID BACKFLOW PREVENTER. A SEPARATE
 PERMIT IS REQUIRED FOR THE BACKFLOW PREVENTER. IF SUCH
 A BACKFLOW PREVENTER IS EXISTING AND IN PLACE, SHOW IT
 ON THE PLAN AS EXISTING. AN UP TO DATE CERTIFICATION
 SHALL BE PROVIDED PRIOR TO FINAL INSPECTION.
  
 5.PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S
 SPECIFICATION FOR THE WATER HEATER AT THE LAVATORY.
 IDENTIFY THE WATER HEATER ON THE WATER DISTRIBUTION
 PLANS. PROVIDE ELECTRICAL CHARACTERISTICS AND GPM
 CAPACITY. SHOW THAT THE GPM CAPACITY WILL MEET THE
 DEMAND OF THE LAVATORY AND THE TWO SINKS.
  
 6.PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S
 SPECIFICATION FOR THE MIXING VALVE AT THE LAVATORY.
 PROVIDE ELECTRICAL CHARACTERISTICS AND GPM CAPACITY.
  
 7.PER WPB FBC PL 603.1, THE WATER SERVICE PIPE SHALL BE
 NOT LESS THAN 3/4 INCH (19.1 MM) IN DIAMETER.
  
 8.PER WPB FBC 107.2.1, PROVIDE CALCULATIONS FOR SIZING
 OF WATER DISTRIBUTION SHOWING COMPLIANCE WITH THE
 PROVISIONS OF FBC PL SECTION 604.
  
 9.PER FBC PL 606.1, FULL-OPEN VALVES SHALL BE INSTALLED
 IN THE FOLLOWING LOCATIONS:
 A.ON THE WATER DISTRIBUTION SUPPLY PIPE AT THE ENTRANCE
 INTO THE STRUCTURE.
 B.ON THE TOP OF EVERY WATER DOWN-FEED PIPE IN
 OCCUPANCIES OTHER THAN ONE- AND TWO-FAMILY RESIDENTIAL
 OCCUPANCIES.
  
 10.REGARDING THE POINT OF USE WATER HEATER DETAIL, THE
 TWO-WAY VALVE FOR COLD WATER TO SINK AND WATER HEATER
 IS NOT COMPLIANT. PER FBC PL 503.1, THE COLD WATER
 BRANCH LINE TO THE WATER HEATER SHALL BE PROVIDED WITH
 A DEDICATED VALVE. THE CORRECT DISTRIBUTION OF HOT
 WATER FROM THE HEATER TO ALL FIXTURES REQUIRING HOT
 WATER IS NOT INDICATED ON THE PLANS AS ONLY THE FIXTURE
 IN THE DETAIL SEEMS TO BE SUPPLIED WITH HOT WATER. PER
 WPB FBC 107.2.1, PROVIDE A DETAIL SHOWING SAID REQUIRED
 DISTRIBUTION. PER FBC PL 602.2, PROVIDE A SHUT OFF
 VALVE FOR THE COLD WATER SUPPLY AND THE HOT WATER
 SUPPLY TO THE FIXTURE.
  
 11.PER FBC EC C404.4, INSULATE HOT WATER PIPING FROM
 WATER HEATER TO THE FIXTURE SUPPLY IN ACCORDANCE WITH
 FBC EC 403.2.10.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  