Plan Review Notes For Permit 20121385 |
Permit Number |
20121385 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2021-03-31 10:38:28 | SFR ADDITION | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) NEW EXTERIOR DOORS AT EXISTING BEDROOM - PLEASE SHOW | | THE EXTERIOR LANDING TO COMPLY WITH FBC R311.3 FLOORS | | AND LANDINGS AT EXTERIOR DOORS. | | THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH | | EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL BE NOT | | LESS THAN THE DOOR SERVED. EVERY LANDING SHALL HAVE A | | DIMENSION OF NOT LESS THAN 36 INCHES (914 MM) MEASURED | | IN THE DIRECTION OF TRAVEL. THE SLOPE AT EXTERIOR | | LANDINGS SHALL NOT EXCEED 1/4 UNIT VERTICAL IN 12 UNITS | | HORIZONTAL (2 PERCENT). | | 2) THE SITE PLAN NEEDS TO SHOW THE SETBACKS FOR THE | | ADDED ROOFED PATIO. | | | | DEFERRED SUBMITTALS: WINDOW AND DOOR PRODUCT APPROVALS, | | ROOFING SYSTEM. | | |
|