Plan Review Notes
Plan Review Notes For Permit 20121361
Permit Number 20121361
Review Stop M
Sequence Number 2
Notes
Date Text
2023-05-09 06:09:121ST REVIEW FMC
 PERMIT: 20121361
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE APPLICATION DOES NOT MENTION ANY MECHANICAL WORK IN
 THIS BUILDING. THERE IS NO SCOPE OF WORK FOR THE
 MECHANICAL SYSTEMS. THERE IS NO INDICATION AS TO THE
 OCCUPANCY OF THIS BUILDING ON ANY DRAWINGS. SHEET M2.1
 IS SHOWING A NEW RTU-9 BUT DOES NOT GIVE AN OCCUPANCY
 IN THE OUTDOOR AIR CALCULATIONS. IF THIS IS TO BE A
 SHELL BUILDING THAT WILL HAVE A CHANGE OF USE AND A
 COMPLETE MECHANICAL DESIGN AT THAT TIME PROVIDE A SCOPE
 OF WORK AND AN APPLICATION FOR WHAT IS BEING COMPLETED
 UNDER THIS PERMIT. FBC 107.3.5
  
 1) SHEET A-4 INDICATES THIS BUILDING TO BE AN I-2
 OCCUPANCY. THE COMPLETE MECHANICAL DESIGN FOR THIS I-2
 SHALL MEET THE REQUIREMENTS OF ASHRAE 170. FMC 407.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  