2023-05-09 06:09:12 | 1ST REVIEW FMC |
| PERMIT: 20121361 |
| |
| CODES IN EFFECT: 2020 |
| |
| FBC- FLORIDA BUILDING CODE |
| FMC- FLORIDA MECHANICAL CODE |
| FEC- FLORIDA ENERGY CONSERVATION |
| FGC- FLORIDA FUEL GAS |
| FEX- FLORIDA EXISTING BUILDING CODE |
| FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| F.S.- FLORIDA STATUTES |
| FAC- FLORIDA ACCESSIBILITY CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| THE APPLICATION DOES NOT MENTION ANY MECHANICAL WORK IN |
| THIS BUILDING. THERE IS NO SCOPE OF WORK FOR THE |
| MECHANICAL SYSTEMS. THERE IS NO INDICATION AS TO THE |
| OCCUPANCY OF THIS BUILDING ON ANY DRAWINGS. SHEET M2.1 |
| IS SHOWING A NEW RTU-9 BUT DOES NOT GIVE AN OCCUPANCY |
| IN THE OUTDOOR AIR CALCULATIONS. IF THIS IS TO BE A |
| SHELL BUILDING THAT WILL HAVE A CHANGE OF USE AND A |
| COMPLETE MECHANICAL DESIGN AT THAT TIME PROVIDE A SCOPE |
| OF WORK AND AN APPLICATION FOR WHAT IS BEING COMPLETED |
| UNDER THIS PERMIT. FBC 107.3.5 |
| |
| 1) SHEET A-4 INDICATES THIS BUILDING TO BE AN I-2 |
| OCCUPANCY. THE COMPLETE MECHANICAL DESIGN FOR THIS I-2 |
| SHALL MEET THE REQUIREMENTS OF ASHRAE 170. FMC 407.1 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |