Plan Review Notes
Plan Review Notes For Permit 20121361
Permit Number 20121361
Review Stop B
Sequence Number 2
Notes
Date Text
2023-06-07 08:43:49WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT:20121361 APPLIED 12/30/2020 / 2017
 FBC-B
 ADD: 5400 EAST AVE.
 CONT: MC CABE BROTHERS CONSTRUCTION
 TEL: 561-771-0047
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. JUNE 07TH/2021
 ACTION: DENIED
  
 1) COMPLIED. PLANS IN SEPARATE FOLDER.
  
 2) SEMI-COMPLIED. SHEET A2- SHELL ONLY NO INTERIOR
 WORK. REMOVE ALL REFERANCES TO OCCUPANCIES & OCCUPANT
 LOADS.
  
 3A) 2ND REQUEST. SEMI-COMPLIED. SURVEY SHOWS FLOOD ZONE
 X AND AH15. THE SURVEY 2ND SHEET DOES NOT SHOW THE
 FINISH FLOOR ELEVATION. THE FINISH FLOOR ELEVATION
 SHOULD BE IN NAVD 88 AS STATED ON SURVEY.
 COMMENT RESPONSE SHEET STATES ELEVATION CERTIFICATE
 PROVIDED BY OWNER NO ELEVATION CERTIFICATE PROVIDED FOR
 2ND REVIEW.
 1ST ROUND OF COMMENTS. PLEASE PROVIDE A UP TO DATE
 SURVEY OF THE PROPERTY, THE BUILDING IS IN A FLOOD ZONE
 AH BFE: 15 FT. IN NAVD 88 AND APPEARS A PORTION OF THE
 BUILDING IS LOCATED WITHIN THIS FLOOD ZONE. PLEASE SHOW
 THE ELEVATION OF THE EXISTING FINISH FLOOR ON THE
 SURVEY AND FLOOR PLAN IN NAVD 88.
 1612.5 FLOOD HAZARD DOCUMENTATION. WEST PALM BEACH MUNI
 CODE. ARTICLE XVII ORDINANCES ARTICLE XVII FLOOD
 PREVENTION & CONTROL
 FBC BUILDING 1612 AND CITY OF WPB CODE OF SECTION
 94-546. STRUCTURE IS IN AN "A" FLOOD ZONE. A FLOOD
 ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE REVIEW
 CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE AN
 ADDITIONAL 6 INCHES/ (12 INCHES OF ELEVATION IF PERMIT
 APPLICATION AFTER SEPT. 12/2016,
 AFTER OCT. 11/ 2017 AN ADDITIONAL ONE FOOT OF FREE
 BOARD WILL BE REQUIRED OR (2) FEET ABOVE BASE FLOOD.
 AFTER OCT. 11/ 2017 THE BUILDING DEPARTMENT WILL HAVE
 ADOPTED THE NEW FLOOD MAPS IN NAVD 88 ELEVATIONS. YOU
 CAN GO TO THE WEBSITE:
 WWW.NGS.NOAA.GOV/TOOLS/VERTCON/VERTCON.HTML FOR
 CONVERSIONS.
  
 3B) 2ND REVIEW. AS INSTRUCTED BY MR. ROBERT BROWN,
 CHIEF BUILDING OFFICIAL PROVIDE A COST BREAK DOWN AS
 PER CONVERSATION 2-10-23. THERE ARE NO FILES FOR A COST
 BREAK DOWN. THE RESPONSE ALSO STATES SEE ATTACHED IS AN
 UP-TO-DATE APPRAISAL OF THE EXISTING BUILDING WHICH
 ALSO IS A MISSING DOCUMENT. .
 1ST ROUND COMMENTS. DETERMINATION OF SUBSTANTIAL
 IMPROVEMENT OR NOT. SUBSTANIAL IMPROVEMENT. SECTION
 94-546 PROVISIONS FOR FLOOD HAZARD REDUCTION. (A)(3)
 ANY ALTERATION, REPAIR, RECONSTRUCTION, OR IMPROVEMENTS
 TO A PROPERTY WHICH THE CUMULATIVE COST FOR ANY FIVE
 YEAR PERIOD EQUALS OR EXCEEDS 50 % OF THE BUILDING
 VALUE AT THE COMMENCEMENT OF THE FIVE YEAR PERIOD SHALL
 MEET THE REQUIREMENTS OF NEW CONSTRUCTION AS CONTAINED
 IN THIS ARTICLE.
 USING THE PALM BEACH COUNTY PROPERTY APPRAISERS
 WEBSITE, THE CURRENT VALUE FOR IMPROVEMENT VALUE
 (BUILDING) IS $2,288749,00 DOLLARS OF VALUE. ONE-HALF
 OF THAT VALUE IS $1,144,374.50 DOLLARS. IF THE DOLLAR
 VALUE OF ANY PERMIT VALUE IS
 $1,144,374,50 OR HIGHER SUBSTANTIAL IMPROVEMENT IS MET,
 REQUIRING COMPLIANCE WITH FLOOD PREVENTION & CONTROL.
  
  
 3B)(1) FIRST ROUND COMMENT, THE VALUE OF PERMIT
 16030222 WHICH EXPIRED WAS $998, 616.00 DOLLARS OF
 WORK, THE PERMIT WAS ABANDONED.
 A PORTION OF WORK WAS ACCOMPLISHED UNDER THIS PERMIT
 WITH A SAID VALUE. PLEASE PROVIDE WHAT DOLLAR VALUE
 WOULD BE PLACED ON THE WORK COMPLETED. A ROOFING PERMIT
 18100490 WAS COMPLETED WITH A DOLLAR VALUE OF
 $233,764.00 OF VALUE.
 THE ROOFING PERMIT AND PROPOSED WORK ALONE COMES TO A
 VALUE OF $710, 628.00 DOLLARS OF VALUE PLUS THE
 PERCENTAGE OF THE PERMIT 16030222. THE PHASE II PORTION
 OF THIS BUILDING (INTERIOR BUILD OUT) WOULD NEED TO BE
 LESS THAN $433, 746.50 WITH THE VALUE OF THE ABANDONED
 PERMIT TAKEN OUT OF THE THIS DOLLAR AMOUNT TO NOT HIT
 SUBSTANTIAL IMPROVEMENT REQUIREMENTS.
 ALL NEW CONSTRUCTION OR SUBSTANTIAL IMPROVEMENT OF ANY
 COMMERCIAL, INDUSTRIAL OR OTHER NONRESIDENTIAL
 STRUCTURE SHALL EITHER HAVE THE LOWEST FLOOR, INCLUDING
 BASEMENT, ELEVATED TO THE LEVEL OF 2 FEET ABOVE THE
 BASE FLOOD ELEVATION OR, TOGETHER WITH ATTENDANT
 UTILITY AND SANITARY FACILITIES, BE FLOODPROOFED SO
 THAT BELOW 2 FEET ABOVE THE FLOOD BASE LEVEL THE
 STRUCTURE IS WATERTIGHT, WITH WALLS SUBSTANTIALLY
 IMPERMEABLE TO THE PASSAGE OF WATER AND WITH STRUCTURAL
 COMPONENTS HAVING THE CAPABILITY OF RESISTING
 HYDROSTATIC AND HYDRODYNAMIC LOADS AND EFFECTS OF
 BUOYANCY. A REGISTERED PROFESSIONAL ENGINEER OR
 ARCHITECT SHALL CERTIFY THAT THE STANDARDS OF THIS
 SUBSECTION ARE SATISFIED. SUCH CERTIFICATION SHALL BE
 PROVIDED TO THE CITY ENGINEER.
  
 3C) 1ST ROUND COMMENT. THERE MAYBE ANOTHER AVENUE YOU
 MAY WANT TO CONSIDER. THE LIDAR IS NOT ALWAYS ACCURATE,
 THE PROCESS OF GETTING A LOMAR FOR HIS PROPERTY
 REMOVING THIS BUILDING FROM THE FLOOD ZONE.
  
 4) 2ND REQUEST. LIFE SAFETY SHEET & A2 FOR THIS PERMIT
 BEING A SHELL PERMIT THERE SHOULD BE NO OCCUPANCY
 CLASSIFICATION SHOWN. THE LIFE SAFETY SHEET SHOWS THE
 PROPOSED USE AS AN I-2 OCCUPANCY. YES YOU CAN PULL THE
 PERMIT FOR A SHELL BUILDING AND USE THE 2017 EXISTING
 BUILDING CODE AS THE REFERENCED CODE. PLEASE BE AWARE
 IN THE 2017 EXISTING BUILDING CODE SECTION 101.2 SCOPE
 AND THE EXCEPTION: FOR THE PURPOSE OF STATE LICENSED
 FACILITIES, SEE CHAPTER 4, SPECIAL OCCUPANCIES, OF THE
 FLORIDA BUILDING CODE, BUILDING. 2017 FBC-BUILDING CODE
 SECTION 450 NURSING HOMES (I-2OCCUPANCIES)
 SECTION450.1.3 EXEMPT NURSING HOMES FROM COMPLIANCE
 WITH THAT CODE. NURSING HOMES MUST COMPLY WITH RULES
 FOR NEW CONSTRUCTION SINCE IN 450.1.5 THEY HAVE TO
 APPLY FOR STATE LICENSURE PURPOSES.
  
 1ST ROUND COMMENT. THE LIFE SAFETY PLAN SHOWS EXITS AND
 EXIT ACCESS TO THE EXITS, BUT WITHOUT A FLOOR PLAN WITH
 PROPOSED WALLS AND ROOM USES, IT IS NOT TRULY A LIFE
 SAFETY PLAN. ADDITIONAL INFORMATION IS REQUIRED.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA
  
  
 5) COMPLIED. +/- WINDOW & DOOR PRESSURES.
  
 6) 2ND REQUEST. NO WINDOW OR DOOR PRODUCT APPROVALS
 WERE SUBMITTED NOR ON SHEET A2 LIST OF DEFERRED
 SUBMITTALS WERE WINDOW AND DOOR PRODUCT APPROVALS
 INCLUDED.
 1ST ROUND OF COMMENTS.2017 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS.
 (B) WINDOWS & MULLIONS.
  
 7) 2ND REQUEST. W. P. B. 107.3.4. PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA
 ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND
 APPROVED IN WRITING (SHOP DRAWING STAMP OF APPROVAL) BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 8)2ND REQUEST. NO WINDOW OR DOOR PRODUCT APPROVALS WERE
 SUBMITTED NOR ON SHEET A2 LIST OF DEFERRED SUBMITTALS
 WERE WINDOW AND DOOR PRODUCT APPROVALS INCLUDED.
 1ST REVIEW CYCLE. 107.3.4.2 DEFERRED SUBMITTALS. FOR
 THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 9) 2ND REQUEST, NO PRODUCT APPROVALS WERE SUBMITTED.
 IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURERS INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 10) COMPLIED 10A-D.
 11) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  