2023-06-07 08:43:49 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT:20121361 APPLIED 12/30/2020 / 2017 |
| FBC-B |
| ADD: 5400 EAST AVE. |
| CONT: MC CABE BROTHERS CONSTRUCTION |
| TEL: 561-771-0047 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: WED. JUNE 07TH/2021 |
| ACTION: DENIED |
| |
| 1) COMPLIED. PLANS IN SEPARATE FOLDER. |
| |
| 2) SEMI-COMPLIED. SHEET A2- SHELL ONLY NO INTERIOR |
| WORK. REMOVE ALL REFERANCES TO OCCUPANCIES & OCCUPANT |
| LOADS. |
| |
| 3A) 2ND REQUEST. SEMI-COMPLIED. SURVEY SHOWS FLOOD ZONE |
| X AND AH15. THE SURVEY 2ND SHEET DOES NOT SHOW THE |
| FINISH FLOOR ELEVATION. THE FINISH FLOOR ELEVATION |
| SHOULD BE IN NAVD 88 AS STATED ON SURVEY. |
| COMMENT RESPONSE SHEET STATES ELEVATION CERTIFICATE |
| PROVIDED BY OWNER NO ELEVATION CERTIFICATE PROVIDED FOR |
| 2ND REVIEW. |
| 1ST ROUND OF COMMENTS. PLEASE PROVIDE A UP TO DATE |
| SURVEY OF THE PROPERTY, THE BUILDING IS IN A FLOOD ZONE |
| AH BFE: 15 FT. IN NAVD 88 AND APPEARS A PORTION OF THE |
| BUILDING IS LOCATED WITHIN THIS FLOOD ZONE. PLEASE SHOW |
| THE ELEVATION OF THE EXISTING FINISH FLOOR ON THE |
| SURVEY AND FLOOR PLAN IN NAVD 88. |
| 1612.5 FLOOD HAZARD DOCUMENTATION. WEST PALM BEACH MUNI |
| CODE. ARTICLE XVII ORDINANCES ARTICLE XVII FLOOD |
| PREVENTION & CONTROL |
| FBC BUILDING 1612 AND CITY OF WPB CODE OF SECTION |
| 94-546. STRUCTURE IS IN AN "A" FLOOD ZONE. A FLOOD |
| ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE REVIEW |
| CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE AN |
| ADDITIONAL 6 INCHES/ (12 INCHES OF ELEVATION IF PERMIT |
| APPLICATION AFTER SEPT. 12/2016, |
| AFTER OCT. 11/ 2017 AN ADDITIONAL ONE FOOT OF FREE |
| BOARD WILL BE REQUIRED OR (2) FEET ABOVE BASE FLOOD. |
| AFTER OCT. 11/ 2017 THE BUILDING DEPARTMENT WILL HAVE |
| ADOPTED THE NEW FLOOD MAPS IN NAVD 88 ELEVATIONS. YOU |
| CAN GO TO THE WEBSITE: |
| WWW.NGS.NOAA.GOV/TOOLS/VERTCON/VERTCON.HTML FOR |
| CONVERSIONS. |
| |
| 3B) 2ND REVIEW. AS INSTRUCTED BY MR. ROBERT BROWN, |
| CHIEF BUILDING OFFICIAL PROVIDE A COST BREAK DOWN AS |
| PER CONVERSATION 2-10-23. THERE ARE NO FILES FOR A COST |
| BREAK DOWN. THE RESPONSE ALSO STATES SEE ATTACHED IS AN |
| UP-TO-DATE APPRAISAL OF THE EXISTING BUILDING WHICH |
| ALSO IS A MISSING DOCUMENT. . |
| 1ST ROUND COMMENTS. DETERMINATION OF SUBSTANTIAL |
| IMPROVEMENT OR NOT. SUBSTANIAL IMPROVEMENT. SECTION |
| 94-546 PROVISIONS FOR FLOOD HAZARD REDUCTION. (A)(3) |
| ANY ALTERATION, REPAIR, RECONSTRUCTION, OR IMPROVEMENTS |
| TO A PROPERTY WHICH THE CUMULATIVE COST FOR ANY FIVE |
| YEAR PERIOD EQUALS OR EXCEEDS 50 % OF THE BUILDING |
| VALUE AT THE COMMENCEMENT OF THE FIVE YEAR PERIOD SHALL |
| MEET THE REQUIREMENTS OF NEW CONSTRUCTION AS CONTAINED |
| IN THIS ARTICLE. |
| USING THE PALM BEACH COUNTY PROPERTY APPRAISERS |
| WEBSITE, THE CURRENT VALUE FOR IMPROVEMENT VALUE |
| (BUILDING) IS $2,288749,00 DOLLARS OF VALUE. ONE-HALF |
| OF THAT VALUE IS $1,144,374.50 DOLLARS. IF THE DOLLAR |
| VALUE OF ANY PERMIT VALUE IS |
| $1,144,374,50 OR HIGHER SUBSTANTIAL IMPROVEMENT IS MET, |
| REQUIRING COMPLIANCE WITH FLOOD PREVENTION & CONTROL. |
| |
| |
| 3B)(1) FIRST ROUND COMMENT, THE VALUE OF PERMIT |
| 16030222 WHICH EXPIRED WAS $998, 616.00 DOLLARS OF |
| WORK, THE PERMIT WAS ABANDONED. |
| A PORTION OF WORK WAS ACCOMPLISHED UNDER THIS PERMIT |
| WITH A SAID VALUE. PLEASE PROVIDE WHAT DOLLAR VALUE |
| WOULD BE PLACED ON THE WORK COMPLETED. A ROOFING PERMIT |
| 18100490 WAS COMPLETED WITH A DOLLAR VALUE OF |
| $233,764.00 OF VALUE. |
| THE ROOFING PERMIT AND PROPOSED WORK ALONE COMES TO A |
| VALUE OF $710, 628.00 DOLLARS OF VALUE PLUS THE |
| PERCENTAGE OF THE PERMIT 16030222. THE PHASE II PORTION |
| OF THIS BUILDING (INTERIOR BUILD OUT) WOULD NEED TO BE |
| LESS THAN $433, 746.50 WITH THE VALUE OF THE ABANDONED |
| PERMIT TAKEN OUT OF THE THIS DOLLAR AMOUNT TO NOT HIT |
| SUBSTANTIAL IMPROVEMENT REQUIREMENTS. |
| ALL NEW CONSTRUCTION OR SUBSTANTIAL IMPROVEMENT OF ANY |
| COMMERCIAL, INDUSTRIAL OR OTHER NONRESIDENTIAL |
| STRUCTURE SHALL EITHER HAVE THE LOWEST FLOOR, INCLUDING |
| BASEMENT, ELEVATED TO THE LEVEL OF 2 FEET ABOVE THE |
| BASE FLOOD ELEVATION OR, TOGETHER WITH ATTENDANT |
| UTILITY AND SANITARY FACILITIES, BE FLOODPROOFED SO |
| THAT BELOW 2 FEET ABOVE THE FLOOD BASE LEVEL THE |
| STRUCTURE IS WATERTIGHT, WITH WALLS SUBSTANTIALLY |
| IMPERMEABLE TO THE PASSAGE OF WATER AND WITH STRUCTURAL |
| COMPONENTS HAVING THE CAPABILITY OF RESISTING |
| HYDROSTATIC AND HYDRODYNAMIC LOADS AND EFFECTS OF |
| BUOYANCY. A REGISTERED PROFESSIONAL ENGINEER OR |
| ARCHITECT SHALL CERTIFY THAT THE STANDARDS OF THIS |
| SUBSECTION ARE SATISFIED. SUCH CERTIFICATION SHALL BE |
| PROVIDED TO THE CITY ENGINEER. |
| |
| 3C) 1ST ROUND COMMENT. THERE MAYBE ANOTHER AVENUE YOU |
| MAY WANT TO CONSIDER. THE LIDAR IS NOT ALWAYS ACCURATE, |
| THE PROCESS OF GETTING A LOMAR FOR HIS PROPERTY |
| REMOVING THIS BUILDING FROM THE FLOOD ZONE. |
| |
| 4) 2ND REQUEST. LIFE SAFETY SHEET & A2 FOR THIS PERMIT |
| BEING A SHELL PERMIT THERE SHOULD BE NO OCCUPANCY |
| CLASSIFICATION SHOWN. THE LIFE SAFETY SHEET SHOWS THE |
| PROPOSED USE AS AN I-2 OCCUPANCY. YES YOU CAN PULL THE |
| PERMIT FOR A SHELL BUILDING AND USE THE 2017 EXISTING |
| BUILDING CODE AS THE REFERENCED CODE. PLEASE BE AWARE |
| IN THE 2017 EXISTING BUILDING CODE SECTION 101.2 SCOPE |
| AND THE EXCEPTION: FOR THE PURPOSE OF STATE LICENSED |
| FACILITIES, SEE CHAPTER 4, SPECIAL OCCUPANCIES, OF THE |
| FLORIDA BUILDING CODE, BUILDING. 2017 FBC-BUILDING CODE |
| SECTION 450 NURSING HOMES (I-2OCCUPANCIES) |
| SECTION450.1.3 EXEMPT NURSING HOMES FROM COMPLIANCE |
| WITH THAT CODE. NURSING HOMES MUST COMPLY WITH RULES |
| FOR NEW CONSTRUCTION SINCE IN 450.1.5 THEY HAVE TO |
| APPLY FOR STATE LICENSURE PURPOSES. |
| |
| 1ST ROUND COMMENT. THE LIFE SAFETY PLAN SHOWS EXITS AND |
| EXIT ACCESS TO THE EXITS, BUT WITHOUT A FLOOR PLAN WITH |
| PROPOSED WALLS AND ROOM USES, IT IS NOT TRULY A LIFE |
| SAFETY PLAN. ADDITIONAL INFORMATION IS REQUIRED. |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA |
| |
| |
| 5) COMPLIED. +/- WINDOW & DOOR PRESSURES. |
| |
| 6) 2ND REQUEST. NO WINDOW OR DOOR PRODUCT APPROVALS |
| WERE SUBMITTED NOR ON SHEET A2 LIST OF DEFERRED |
| SUBMITTALS WERE WINDOW AND DOOR PRODUCT APPROVALS |
| INCLUDED. |
| 1ST ROUND OF COMMENTS.2017 FBC-B 1609.1.2 PROTECTION OF |
| OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE |
| 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY |
| OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS, MULLIONS. |
| (B) WINDOWS & MULLIONS. |
| |
| 7) 2ND REQUEST. W. P. B. 107.3.4. PRODUCT APPROVALS. |
| THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA |
| ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND |
| APPROVED IN WRITING (SHOP DRAWING STAMP OF APPROVAL) BY |
| THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC. |
| |
| 8)2ND REQUEST. NO WINDOW OR DOOR PRODUCT APPROVALS WERE |
| SUBMITTED NOR ON SHEET A2 LIST OF DEFERRED SUBMITTALS |
| WERE WINDOW AND DOOR PRODUCT APPROVALS INCLUDED. |
| 1ST REVIEW CYCLE. 107.3.4.2 DEFERRED SUBMITTALS. FOR |
| THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE |
| DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE |
| TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. |
| |
| 9) 2ND REQUEST, NO PRODUCT APPROVALS WERE SUBMITTED. |
| IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1 |
| INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| ACCORDANCE WITH APPROVED MANUFACTURERS INSTRUCTIONS. |
| FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| LOADS AND SPACING USED IN THE TESTS. |
| |
| 10) COMPLIED 10A-D. |
| 11) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| 19 |
| IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| 561-718-9724. |
| WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| RETIRED. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |