Plan Review Notes
Plan Review Notes For Permit 20121355
Permit Number 20121355
Review Stop P
Sequence Number 1
Notes
Date Text
2021-01-22 17:18:281ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20121355
 1/22/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) P-1: PROVIDE A FIRESTOPPING ASSEMBLY DETAIL TO SEAL
 THE ANNULAR SPACE AROUND THE NEW SINK DRAIN PIPING
 PENETRATIONS- SECTION 315.1 FBC P AND SECTION 714.4.1.2
 FBC B. PLEASE CLARIFY IF THE NEW SINK DRAIN
 PENETRATIONS WILL REQUIRE THE FLOOR TO BE X-RAYED TO IN
 ORDER TO LOCATE REINFORCING STEEL OR POST STRESSED
 FLOOR TENDONS- SECTION 107.2.1 WPB.
  
 2) P-1: PROVIDE A PLUMBING FIXTURE SCHEDULE THAT
 INCLUDES THE MAKES, MODELS, DIMENSIONS AND LISTING
 NUMBERS OF THE NEW SINKS- SECTIONS 418 & 424 FBC P. THE
 SCHEDULE ON THE PLAN INDICATES A JANITOR SINK WHICH
 NEEDS TO BE IDENTIFIED ON THE PLAN. IT IS NOT CLEAR
 WHAT THE REST OF THE SINKS IN THE TREATMENT ROOMS ARE
 TO BE USED FOR BECAUSE THEY ARE LISTED AS "BY OWNER".
 PLEASE CLARIFY THE USE OF THE SINKS AND NOTE THAT
 DEFERRED SUBMITTALS ARE ALLOWED, BUT ALL SPECIFICATIONS
 MUST BE REVIEWED AND APPROVED BY THE DESIGN
 PROFESSIONAL IN CHARGE- SECTION 107.3.4.1 WPB.
  
 3) P-1: CLARIFY IF THE NEW DRAIN PIPES WILL BE RUNNING
 THROUGH A PLENUM SPACE AND INDICATE THE TYPE OF PIPE
 MATERIALS TO BE INSTALLED- SECTION 303.2 FBC P AND
 107.2.1 WPB.
  
 4) P1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE WATER
 HEATER INDICATING MAKE AND MODEL AND EFFICIENCY RATING
 IN COMPLIANCE WITH TABLE C404.2 FBC EC.
  
 5) P-1: PROVIDE AN INSTALLATION DETAIL OR ELEVATION
 VIEW OF THE WATER HEATER SHOWING:
  
 A) ACCESS FOR SERVICE, INSPECTION AND REPLACEMENT-
 SECTION 502.5 FBC P.
 B) WATER PIPING CONNECTIONS- SECTIONS 503 & 504 FBC P.
 C) MEANS OF CONTROLLING THERMAL EXPANSION- SECTION
 607.3 FBC P.
 D) LOCATION OF RECIRCULATION PUMP- PLEASE INCLUDE MAKE
 AND MODEL SPECIFICATION- SECTION 607.2.1 FBC P.
 E) TYPE AND SIZE OF WATER HEATER PAN- SECTION 504.7 &
 504.7.1 FBC P.
 F) TYPE AND SIZE OF DRAIN PAN PIPE, PIPE RUN, AND
 DISCHARGE LOCATION- 504.7.2 FBC P.
  
 6) SECTION 212.3 REQUIRES 5%, BUT NO FEWER THAN ONE, OF
 EACH TYPE IN EACH ACCESSIBLE ROOM TO BE IN COMPLIANCE
 WITH SECTION 606 FBC ACC. PLEASE PROVIDE THE FOLLOWING
 DETAILS PER THE FBC ACC.
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 NEW SINKS- SECTIONS 212.3 AND 606.
 B) KNEE AND TOE CLEARANCES FOR THE NEW SINKS- 606.2,
 305, & 306.
 C) HEIGHT OF THE SINK RIMS OR COUNTER SURFACES ABOVE
 THE FINISH FLOORS- 606.3.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  