2021-02-19 13:52:28PLEASE PROVIDE THE DEVELOPED LENGTH TO THE FARTHEREST
 APPLIANCE FROM THE GAS SERVICE. FBC FG 402.4
 PLEASE SHOW THE PRESSURE OF THE EXISTING PIPING SYSTEM.
 FBC107.2.1
 PLASTIC PIPING MUST MEET SECTION 404.17, IT IS FOR
 OUTDOORS UNDERGROUND ONLY.
 PLEASE PROVIDE A GAS RISER DIAGRAM SHOWING ALL OF THE
 PIPING IN THIS SYSTEM. THE NOTE ADDED INDICATES THAT
 THE PIPING GOING INTO THE HOUSE IS THREE QUARTER INCH
 BUT THE INFORMATION EXPLAINING THE LENGTH OF PIPING
 GOING TO WATER HEATER AND THE HOUSE APPLIANCES
 INDICATES THIS PIPE AS ONE HALF INCH. PLEASE BE
 CONSISTENT
 THE PIPING SYSTEM SHOULD SHOW THE LOCATION OF ALL THE
 ADDED REGULATORS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER