Date |
Text |
2021-01-14 06:02:03 | PETER E VALENTI |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6673 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| FBC M = FBC MECHANICAL |
| FBC FG = FBC FUEL GAS |
| |
| BUILDING REVIEW DENIED: |
| |
| THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A |
| DEMO PERMIT PER FLORIDA BUILDING CODE, BUILDING 3303: |
| |
| 1. UTILITY RELEASE - FLORIDA POWER & LIGHT (ELECTRIC) |
| RELEASE OF SERVICE CONFIRMATION |
| |
| (STILL PENDING PLAN REVIEW APPROVAL OF ELECTRIC PERMIT |
| # 20121183). |
| |
| |
| |
| 3. UTILITY RELEASE - CITY OF WEST PALM BEACH WATER |
| DEPARTMENT, REQUEST FOR METER PULL, ON THEIR FORM |
| "DEMOLITION APPLICATION" |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED, |
| THEN A PARTIAL RELEASE WILL BE NOTED ON THEIR FORM. |
| FAX THE COMPLETED "DEMOLITION APPLICATION" FORM TO |
| 561-822-2183. |
| |
| (STILL PENDING THE RETURNED UTILITY DEMO APPLICATION |
| FRO THE UTILITY DEPARTMENT AND APPROVED PERMIT NUMBERS |
| FOR BACKFLOW PREVENTER OR HYDRANT METER IF THOSE |
| METHODS ARE TO BE USED FOR WATERING DOWN SITE OTHERWISE |
| PROVIDE INFORMATION FOR ALTERNATE METHOD OF WATERING |
| DOWN SITE). |
| |
| |
| 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED (SUBMIT |
| APPLICATION TO BUILDING DIVISION); SCHEDULE A FINAL |
| PLUMBING #703. |
| |
| (STILL PENDING THE APPROVED PERMIT # FOR SEWER LATERAL |
| CAPPING). |
| |
| |
| 9. PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE |
| CONTRACTOR, ON LETTERHEAD, STATING THAT THE |
| INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM |
| COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH |
| COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE |
| GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS |
| REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: |
| HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE |
| S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- |
| RENOVATION.HTML |
| |
| (STILL PENDING). |
| |
| |
| |
| BACKFLOW - BEFORE SCHEDULING THE 703, THE BACKFLOW |
| DEVICE NEEDS TO BE TESTED AND CERTIFIED BY THE CITY?S |
| UTILITIES DEPT, 561-822-2244. |
| |