2021-01-05 10:36:02 | 01/05/20 1ST REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. PLEASE PROVIDE UNDER CODES, THE YEAR, PLUMBING |
| REFERENCED USED PER THE WPB AMENDMENTS TO THE FBC SEC. |
| 101.4 REFERENCED CODES. ON PAGE A.0, IT REFERENCES THE |
| BUIDING CODE, AND THESE PLANS ARE UNDER THE RESIDENTIAL |
| CODE FOR THE DWELLING; PLEASE CLARIFY. |
| |
| 2. A SEPARATE PERMIT WILL BE REQUIRED FOR DEMOLITION |
| AND CAP OFF PLUMBING PER THE WPB AMENDMENTS TO FBC SEC. |
| 105.1. PLEASE PROVIDE A WATER SOURCE EITHER ON A FIRE |
| HYDRANT OR WITH A BACKFLOW DEVICE THAT REQUIRES A |
| PERMIT FOR THE DEMO WORK. |
| |
| 3. ON SHEET P.3, |
| |
| A. THE WASHING MACHINE IS SHOWN ON A STANDPIPE BELOW |
| THE SLAB, WHICH EXCEEDS THE 42" MAX PER THE 2017 FBC |
| SEC. R 2706.1.1 |
| |
| B. THE VENT IS ON A DRY VENT CONNECTING TO A HORIZONTAL |
| DRAIN SHALL CONNECT ABOVE THE HORIZONTAL DRAIN PIPE'S |
| CENTERLINE PER THE 2017 R 3104.3 VENT CONNECTION TO THE |
| DRAINAGE SYSTEM. PLEASE SHOE CONNECTION ON A SANITARY |
| FITTING TO P-TRAP. |
| |
| 4. THE UPSTAIRS DOUBLE LAV IS MISSING THE SECOND |
| P-TRAP; PLEASE CORRECT PER THE WPB AMENDMENTS TO THE |
| FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 5. THE TANKLESS HEATER HAS PIPES NOT IN CONDITION SPACE |
| AND NEEDS TO BE INSULATED WITH A MINIMUM R-3 PER THE |
| 2017 FBC SEC. RE 403.5.3. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |