2021-01-05 11:10:48 | 01/05/20 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. PLEASE PROVIDE A DIMENSION ON A HOUSE PLAN SHOWING |
| THE TANK-LESS WATER HEATER'S LOCATION AND THE LOCATION |
| AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER |
| HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE |
| HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC. |
| 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 2. GAS UNITS REQUIRE CONDENSATE, AND THEY NEED TO BE 1' |
| AWAY FROM THE STRUCTURE PER THE 2017 FBC SEC R318.5. |
| |
| 3. PLEASE PROVIDE A SPECIFICATION THAT SHOWS LISTED AND |
| LABELED IN ACCORDANCE WITH A SYMBOL OR OTHER |
| IDENTIFYING MARK OF A NATIONALLY RECOGNIZED TESTING |
| LABORATORY, INSPECTION AGENCY, OR OTHER ORGANIZATION |
| CONCERNED WITH PRODUCT EVALUATION THAT MAINTAINS |
| PERIODIC INSPECTION OF THE PRODUCTION OF THE |
| ABOVE-LABELED ITEMS AND WHOSE LABELING INDICATES EITHER |
| THAT THE EQUIPMENT, MATERIAL OR PRODUCT MEETS |
| IDENTIFIED STANDARDS OR HAS BEEN TESTED AND FOUND |
| SUITABLE FOR A SPECIFIED PURPOSE. |
| |
| 4. PLEASE SHOW ALL REGULATORS AND UNIONS IN FRONT OF |
| REGULATOR 1' OF EITHER SIDE PER THE 2017 FBC RES. SEC |
| G2421.2 OR 2017 FBC FG SEC 410.2. |
| |
| 5. NEED A HARD CAP FOR A FUTURE FIRE PIT; PLEASE SHOW |
| ON GAS ISOMERIC G.1 APPLIANCE SHUTOFF 2017 FBC FG SEC. |
| 409.5 OR 2017 FBC RES. SEC. G2401.1.3. |
| |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |