Plan Review Notes
Plan Review Notes For Permit 20121326
Permit Number 20121326
Review Stop B
Sequence Number 1
Notes
Date Text
2021-01-22 18:10:59NEW SINGLE FAMILY RESIDENCE (R3)BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 PERMIT #20121326
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.5.1 FBC-ENERGY CONSERVATION.
 NOTE: PLEASE MAKE SURE CALCULATIONS ARE SIGNED BY ALL
 THE REQUIRED PARTIES, INCLUDING THE OWNER OR AUTHORIZED
 AGENT TO AVOID CONFLICT/DELAYS.
  
 THE ENERGY FORM R405-2017 IS REQUIRED TO BE SIGNED AND
 DATED BY THE OWNER, ARCHITECT OR OWNER?S LEGALLY
 DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION,
 6TH EDITION (2017) PRIOR TO RECEIVING THE PERMIT TO
 BEGIN CONSTRUCTION.
  
 2- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 3- MISSING SHEET A2.1 LISTED ON THE SHEET LIST ON SHEET
 A.0. THIS SHEET HAS THE WINDOWS AND DOORS SCHEDULES.
 UNABLE TO REVIEW EGRESS WINDOWS (SEC. R310.2.1
 FBC-RESIDENTIAL AND IF SECOND FLOOR WINDOWS WILL
 REQUIRE WINDOW FALL PROTECTION (SEC. R312.2
 FBC-RESIDENTIAL). PLEASE PROVIDE THIS SHEET. SEC.
 107.2.1 CITY AMENDMENTS.
  
 4- FOUNDATION PLAN ON SHEET S.1:
 EXTERIOR FOOTINGS SHALL BE PLACED NOT LESS THAN 12
 INCHES BELOW GRADE AS REQUIRED BY SEC. R403.1.4
 FBC-RESIDENTIAL. REVISE DEPTH OF FOOTINGS AS REQUIRED.
 NOTE: COORDINATE FOOTING DEPTH WITH THE REQUIRED
 CLEARANCE REQUIRED ABOVE GRADE FOR TERMITE INSPECTION.
 SEC. R318.7 FBC-RESIDENTIAL.
  
 5- SHEET S.2.1:
 REVISE THE ROOF NET UPLIFT DIAGRAM. THE UPPER ZONE OF
 THE GABLE END IS ZONE #3 NOT ZONE #2. SEE FIGURE
 R301.2(7) FBC-RESIDENTIAL AND REVISE AS REQUIRED.
  
 6- SHEET A.1:
 A)NEED BATHROOM WITH A DOOR THAT PROVIDES 29" MIN.
 CLEAR OPENING AS REQUIRED BY SEC. R320 FBC-RESIDENTIAL.
 FIRST FLOOR BATHROOM (MASTER BATH/POWDER ROOM) DOESN'T
 PROVIDE DOOR WITH 29" CLEAR OPENING WHEN ENTERING THE
 POWDER ROOM. REVISE AS REQUIRED.
  
 B)STAIRWAY ON THE 1ST FLOOR PLAN SHOWS (17)RISERS @
 7.76 INCHES. THIS EXCEEDS THE MAXIMUM RISER HEIGHT OF
 7-3/4 INCHES REQUIRED BY SEC. R311.7.5.1
 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 C)GROUND FLOOR ON SHEET A.1 SHOWS A PREFABRICATED
 PULL-DOWN ACCESS LADDER. SPECIFY THE ADDITIONAL ATTIC
 LIVE LOADS AS REQUIRED BY TABLE R301.5 FBC-RESIDENTIAL.
 ALSO, SPECIFY SIZE OF ATTIC ACCESS OPENING (SEC. R807
 FBC-RESIDENTIAL).
  
 7- SHEET A.1.1: SPECIFY ATTIC ACCESS SIZE AND LOCATION
 SHOWING COMPLIANCE WITH SEC. R807 FBC-RESIDENTIAL.
  
 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)OVERHEAD GARAGE DOOR.
 B)METAL ROOFING.
 C)ALL WINDOW TYPES SHOWN ON PLANS AND WINDOW SCHEDULES.
 D)ENTRY DOOR IF DIFFERENT THAN ALL OTHER EXTERIOR
 DOORS.
 E)OVERHEAD GARAGE DOOR
  
 NOTE: CLARIFY WHY SUBMITTING PRODUCT APPROVAL FOR
 MULLIONS. PLANS DON'T SHOW ANY MULLIONS.
  
 9- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 10- HOUSE IS DESIGNED WITH UNVENTED ATTIC. ARCHITECT IS
 SPECIFYING R-30 SPRAY INSULATION. PROVIDE ICC
 EVALUATION REPORT FOR THE FOAM INSULATION TO VERIFY
 COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 11- DEFERRED SUBMITTAL:
 A)PROVIDE GLAZED RAILINGS SHOP DRAWINGS (REVIEWED BY
 ARCHITECT OF RECORD). NOTE: TABLE R301.5
 FBC-RESIDENTIAL. NEED A SAFETY FACTOR OF 4. SEE NOTE
 "H".
  
 B)BALCONY CABLE RAILINGS SHOP DRAWINGS (REVIEWED BY
 ARCHITECT OF RECORD).
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]