2021-01-22 18:10:59 | NEW SINGLE FAMILY RESIDENCE (R3)BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| PERMIT #20121326 |
| |
| 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| R101.5.1 FBC-ENERGY CONSERVATION. |
| NOTE: PLEASE MAKE SURE CALCULATIONS ARE SIGNED BY ALL |
| THE REQUIRED PARTIES, INCLUDING THE OWNER OR AUTHORIZED |
| AGENT TO AVOID CONFLICT/DELAYS. |
| |
| THE ENERGY FORM R405-2017 IS REQUIRED TO BE SIGNED AND |
| DATED BY THE OWNER, ARCHITECT OR OWNER?S LEGALLY |
| DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS |
| REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, |
| 6TH EDITION (2017) PRIOR TO RECEIVING THE PERMIT TO |
| BEGIN CONSTRUCTION. |
| |
| 2- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| FOLLOWING: |
| R401.3 FBC-RESIDENTIAL. |
| SEC. 107.2.5 CITY AMENDMENTS. |
| SEC. 110.9 CITY AMENDMENTS. |
| |
| 3- MISSING SHEET A2.1 LISTED ON THE SHEET LIST ON SHEET |
| A.0. THIS SHEET HAS THE WINDOWS AND DOORS SCHEDULES. |
| UNABLE TO REVIEW EGRESS WINDOWS (SEC. R310.2.1 |
| FBC-RESIDENTIAL AND IF SECOND FLOOR WINDOWS WILL |
| REQUIRE WINDOW FALL PROTECTION (SEC. R312.2 |
| FBC-RESIDENTIAL). PLEASE PROVIDE THIS SHEET. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| 4- FOUNDATION PLAN ON SHEET S.1: |
| EXTERIOR FOOTINGS SHALL BE PLACED NOT LESS THAN 12 |
| INCHES BELOW GRADE AS REQUIRED BY SEC. R403.1.4 |
| FBC-RESIDENTIAL. REVISE DEPTH OF FOOTINGS AS REQUIRED. |
| NOTE: COORDINATE FOOTING DEPTH WITH THE REQUIRED |
| CLEARANCE REQUIRED ABOVE GRADE FOR TERMITE INSPECTION. |
| SEC. R318.7 FBC-RESIDENTIAL. |
| |
| 5- SHEET S.2.1: |
| REVISE THE ROOF NET UPLIFT DIAGRAM. THE UPPER ZONE OF |
| THE GABLE END IS ZONE #3 NOT ZONE #2. SEE FIGURE |
| R301.2(7) FBC-RESIDENTIAL AND REVISE AS REQUIRED. |
| |
| 6- SHEET A.1: |
| A)NEED BATHROOM WITH A DOOR THAT PROVIDES 29" MIN. |
| CLEAR OPENING AS REQUIRED BY SEC. R320 FBC-RESIDENTIAL. |
| FIRST FLOOR BATHROOM (MASTER BATH/POWDER ROOM) DOESN'T |
| PROVIDE DOOR WITH 29" CLEAR OPENING WHEN ENTERING THE |
| POWDER ROOM. REVISE AS REQUIRED. |
| |
| B)STAIRWAY ON THE 1ST FLOOR PLAN SHOWS (17)RISERS @ |
| 7.76 INCHES. THIS EXCEEDS THE MAXIMUM RISER HEIGHT OF |
| 7-3/4 INCHES REQUIRED BY SEC. R311.7.5.1 |
| FBC-RESIDENTIAL. REVISE AS REQUIRED. |
| |
| C)GROUND FLOOR ON SHEET A.1 SHOWS A PREFABRICATED |
| PULL-DOWN ACCESS LADDER. SPECIFY THE ADDITIONAL ATTIC |
| LIVE LOADS AS REQUIRED BY TABLE R301.5 FBC-RESIDENTIAL. |
| ALSO, SPECIFY SIZE OF ATTIC ACCESS OPENING (SEC. R807 |
| FBC-RESIDENTIAL). |
| |
| 7- SHEET A.1.1: SPECIFY ATTIC ACCESS SIZE AND LOCATION |
| SHOWING COMPLIANCE WITH SEC. R807 FBC-RESIDENTIAL. |
| |
| 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| 61G20-3.001 FOR |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO |
| INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT |
| APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL): |
| |
| A)OVERHEAD GARAGE DOOR. |
| B)METAL ROOFING. |
| C)ALL WINDOW TYPES SHOWN ON PLANS AND WINDOW SCHEDULES. |
| D)ENTRY DOOR IF DIFFERENT THAN ALL OTHER EXTERIOR |
| DOORS. |
| E)OVERHEAD GARAGE DOOR |
| |
| NOTE: CLARIFY WHY SUBMITTING PRODUCT APPROVAL FOR |
| MULLIONS. PLANS DON'T SHOW ANY MULLIONS. |
| |
| 9- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 10- HOUSE IS DESIGNED WITH UNVENTED ATTIC. ARCHITECT IS |
| SPECIFYING R-30 SPRAY INSULATION. PROVIDE ICC |
| EVALUATION REPORT FOR THE FOAM INSULATION TO VERIFY |
| COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL. |
| NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN |
| WRITING PRIOR TO SUBMITTAL TO THIS OFFICE. |
| |
| 11- DEFERRED SUBMITTAL: |
| A)PROVIDE GLAZED RAILINGS SHOP DRAWINGS (REVIEWED BY |
| ARCHITECT OF RECORD). NOTE: TABLE R301.5 |
| FBC-RESIDENTIAL. NEED A SAFETY FACTOR OF 4. SEE NOTE |
| "H". |
| |
| B)BALCONY CABLE RAILINGS SHOP DRAWINGS (REVIEWED BY |
| ARCHITECT OF RECORD). |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |