2021-01-12 13:42:31REST ROOM REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DOOR SWING INTO CORRIDOR CANNOT BLOCK EGRESS PER FBC
 1005.7.1 DOORS.
 DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED
 WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY
 POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE
 THAN ONE-HALF.
 MINIMUM CORRIDOR SIZE (36") FBC TABLE 1020.2
 2) IT IS UNCLEAR AS TO THE LENGTH OF THE TOILET SIDE
 GRAB BAR - PLEASE CLARIFY FBC 604.5.1
 3) PLEASE CLARIFY THE FIXTURE CLEAR FLOOR SPACE BY
 ADDING THE DIMENSIONS FBC 305.3
  