Plan Review Notes For Permit 20121291 |
Permit Number |
20121291 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-01-12 13:42:31 | REST ROOM REMODEL | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) DOOR SWING INTO CORRIDOR CANNOT BLOCK EGRESS PER FBC | | 1005.7.1 DOORS. | | DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED | | WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY | | POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE | | THAN ONE-HALF. | | MINIMUM CORRIDOR SIZE (36") FBC TABLE 1020.2 | | 2) IT IS UNCLEAR AS TO THE LENGTH OF THE TOILET SIDE | | GRAB BAR - PLEASE CLARIFY FBC 604.5.1 | | 3) PLEASE CLARIFY THE FIXTURE CLEAR FLOOR SPACE BY | | ADDING THE DIMENSIONS FBC 305.3 | | |
|