2021-01-04 10:49:35PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THIS HOUSE IS LOCATED ON A LARGE LAKE THAT MAKES IT
 EXPOSURE CATEGORY D FOR WIND PRESSURES. THE REQUIRED
 NEGATIVE (UPLIFT) PRESSURES EXCEED THE -86 PSF FOR THE
 FASTENING SPECIFIED IN THE PRODUCT APPROVAL FOR THE
 CORNER AREAS. FROM TABLE R301.2(2) COMPONENT AND
 CLADDING LOADS FOR EXPOSURE BE ROOF ZONE 3 FOR 170 MPH
 WITH A 10 SQFT TRIBUTARY AREA THE NEGATIVE PRESSURE IS
 -73 PSF. TABLE R301.2(3) FOR HEIGHT AND EXPOSURE
 ADJUSTMENT COEFFIENTS HAS 1.47 FOR EXPOSURE D WITH A
 15' MEAN ROOF HEIGHT. THEREFORE THE REQUIRED UPLIFT
 PRESSURE IS -73 PSF TIMES 1.47 EQUALS -107.31PSF. THIS
 EXCEEDS THE PRESSURES IN THE PRODUCT APPROVAL. FBC 301
  
 2) SUBMIT PRODUCT APPROVALS FOR THE TWO SOLAR ATTIC
 VENTILATORS WITH ADEQUATE DESIGN PRESSURES. FBC 107.3.4
 - PROVIDE TWO SETS OF PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001 PER
 FLORIDA STATUTE 553.842 (5) THAT HAVE BEEN REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD. PROVIDE
 TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA NUMBERS
 INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN
 PRESSURES FOR EACH OF THE DIFFERENT ROOFING PRODUCTS,
 WINDOW TYPES (GLASS TYPES), STRUCTURAL MULLIONS AND
 EXTERIOR DOOR TYPES. ONLY ONE SET IS REQUIRED TO BE
 UPLOADED FOR ELECTRONICALLY SUBMITTED DOCUMENTS.
  
 3) SHOW THE ROOF ZONE LOCATIONS FOR THE SOLAR ATTIC
 VENTLATORS. FBCR-301
  