Plan Review Notes
Plan Review Notes For Permit 20121242
Permit Number 20121242
Review Stop E
Sequence Number 1
Notes
Date Text
2021-01-07 13:51:45PLAN REVIEW / ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE ACTUAL TRANSFORMER SECONDARY FAULT CURRENT
 FROM UTILITY.
  
 AIC RATING OF SERVICE DISCONNECT AND PANEL
  
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3404.2 & FBC RE E3606.3
  
 FBC R E3606.3AVAILABLE SHORT-CIRCUIT CURRENT.
 SERVICE EQUIPMENT SHALL BE SUITABLE FOR THE MAXIMUM
 FAULT CURRENT AVAILABLE AT ITS SUPPLY TERMINALS, BUT
 NOT LESS THAN 10,000 AMPERES. (110.9)
 E3706.1PANELBOARD RATING.
 ALL PANELBOARDS SHALL HAVE A RATING NOT LESS THAN THAT
 OF THE MINIMUM SERVICE OR FEEDER CAPACITY REQUIRED FOR
 THE CALCULATED LOAD. (408.30)
  
 E3404.2INTERRUPTING RATING.
  
 EQUIPMENT INTENDED TO INTERRUPT CURRENT AT FAULT LEVELS
 SHALL HAVE A MINIMUM INTERRUPTING RATING OF 10,000
 AMPERES. EQUIPMENT INTENDED TO INTERRUPT CURRENT AT
 LEVELS OTHER THAN FAULT LEVELS SHALL HAVE AN
 INTERRUPTING RATING AT NOMINAL CIRCUIT VOLTAGE OF NOT
 LESS THAN THE CURRENT THAT MUST BE INTERRUPTED. (110.9)
  
 PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL. NEC
 110.3, 110.9; FBC RE E3606.4
  
 PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE MARKED
 WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT
 AVAILABLE PER NEC 110.24 & FBC RE E3606.4
  
 2. DELETE-N/A
  
 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved