Plan Review Notes
Plan Review Notes For Permit 20121235
Permit Number 20121235
Review Stop B
Sequence Number 2
Notes
Date Text
2021-04-12 15:31:57ADDING SECURITY GATES
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) OVERHEAD ROLL UP GATE DRAWINGS SHOWS A WIND PRESSURE
 OF (-10 PSF) WHICH WILL NOT MEET THE REQUIRED WIND
 PRESSURES FOR THAT OPENING. WILL THERE BE SIGNAGE
 PROVIDED AS TO WHEN THE ROLL UP SCREEN DOOR WILL NEED
 TO BE IN THE ROLLED UP POSITION? FBC 2002.7 (2) WHERE
 SCREEN ENCLOSURES ARE DESIGNED IN ACCORDANCE WITH THE
 SCREEN REMOVAL ALTERNATES OF THIS SECTION, REMOVABLE
 SCREEN MAY CONSIST OF REMOVABLE PANELS, RETRACTABLE
 PANELS, OR BY DESIGNATING SPECIFIC SCREEN PANELS IN THE
 DESIGN IN WHICH THE SCREEN IS TO BE REMOVED BY CUTTING
 THE SCREEN. REMOVABLE PANELS SHALL BE REMOVED,
 RETRACTABLE PANELS SHALL BE PLACED IN THE RETRACTED
 POSITION WITHOUT INCREASING THE LOAD ON THE AFFECTED
 AREA. SCREEN DESIGNATED IN THE DESIGN TO BE CUT SHALL
 BE COMPLETELY CUT WHEN WIND SPEEDS ARE FORECAST TO
 EXCEED 75 MPH. (4) WHERE SCREEN ENCLOSURES ARE DESIGNED
 IN ACCORDANCE WITH THE SCREEN REMOVAL ALTERNATES OF
 THIS SECTION, RETRACTABLE SCREEN PANELS, REMOVABLE
 SCREEN PANELS, AND SCREEN PANELS IDENTIFIED TO BE CUT
 SHALL BE CLEARLY IDENTIFIED ON ADJACENT STRUCTURAL
 MEMBERS WITH HIGHLY VISIBLE PERMANENT LABELS, AT EACH
 PANEL, OR BY OTHER MEANS APPROVED BY THE LOCAL BUILDING
 DEPARTMENT.
 2) TRELLIS WALL SYSTEM TO BE DEFERRED.
  