Plan Review Notes
Plan Review Notes For Permit 20121235
Permit Number 20121235
Review Stop Z
Sequence Number 1
Notes
Date Text
2021-01-07 10:32:09STAFF DOES NOT SUPPORT THE DESIGN OF THE FENCING AROUND
 THE STAIRS. UNDERSTANDING SECURITY, THE FENCING NEEDS
 TO BE ARCHITECTURALLY COMPATIBLE WITH THE DESIGN OF THE
 STRUCTURE, PLEASE EVALUATE OTHER OPTIONS FOR
 ARCHITECTURALLY ENHANCED FENCING. THE SCREENING FORM
 THE UPPER FLOORS COULD BE CONTINUED DOWN FOR
 CONSISTENCY AND SECURITY
  
 LOCATION OF BURIED MOUNTED CAR-HEIGHT PEDESTAL ON SOUTH
 SIDE CANNOT ENCROACH INTO THE CITY ROW - PLEASE
 RELOCATE ONTO PRIVATE PROPERTY
  
 PLEASE INDICATE TIMING OF GARAGE GATE CLOSURES - WILL
 THESE ONLY BE CLOSED WHEN THE OFFICE IS CLOSED FOR
 BUSINESS?
  
 THE LOCATION OF THE PROPOSED GATE APPURTENCES AT THE
 SOUTH ENTRANCE APPEAR TO INTERFERE WITH THE SOUTHERN
 MOST PARKING SPACE INSIDE THE GARAGE - PARKING SPACES
 REQUIRED TO HAVE 8.6 WIDE, AND ADDITIONAL ONE FOOT IF
 NEXT TO WALL. THIS PARKING SPACE MAY NEED TO BE REMOVED
  
 HOW WILL THE PROPOSED PARKING GARAGE SYSTEM WORK WITH
 THE CEILLING MOUNTED PIPES AND EQUIPMENT WITHIN THE
 GARAGE?
  
  