Plan Review Notes
Plan Review Notes For Permit 20121235
Permit Number 20121235
Review Stop B
Sequence Number 1
Notes
Date Text
2021-01-15 15:09:01ADDING SECURITY GATES
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) GATES AND OVERHEAD ROLLUP DOOR ARE SUBJECT TO WIND
 LOADS PLEASE SHOW ON THE DRAWINGS ALL ATTACHMENTS FOR
 SUCH OR PROVIDE MIAMI DADE OR FLORIDA STATE PRODUCT
 APPROVALS WITH WIND DESIGN PRESSURES THAT MEET OR
 EXCEED THE REQUIRED WIND PRESSURES FOR THE SPECIFIC
 OPENING. FBC 1609
 2) DRAWINGS SHOW CODE USED FOR DESIGN AS 2017 FBC -
 CODE IN EFFECT HAS CHANGED TO 2020 FBC - PLEASE REVISE
 THE DRAWINGS TO REFLECT THE CODE IN EFFECT.
 3) PROVIDE SIGNAGE FOR THE FOLLOWING FIX - FBC 1011.7.4
 ENCLOSURES UNDER EXTERIOR STAIRWAYS.
 THERE SHALL NOT BE ENCLOSED USABLE SPACE UNDER EXTERIOR
 EXIT STAIRWAYS UNLESS THE SPACE IS COMPLETELY ENCLOSED
 IN 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION. THE OPEN
 SPACE UNDER EXTERIOR STAIRWAYS SHALL NOT BE USED FOR
 ANY PURPOSE.