Plan Review Notes For Permit 20121235 |
Permit Number |
20121235 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-01-15 15:09:01 | ADDING SECURITY GATES | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) GATES AND OVERHEAD ROLLUP DOOR ARE SUBJECT TO WIND | | LOADS PLEASE SHOW ON THE DRAWINGS ALL ATTACHMENTS FOR | | SUCH OR PROVIDE MIAMI DADE OR FLORIDA STATE PRODUCT | | APPROVALS WITH WIND DESIGN PRESSURES THAT MEET OR | | EXCEED THE REQUIRED WIND PRESSURES FOR THE SPECIFIC | | OPENING. FBC 1609 | | 2) DRAWINGS SHOW CODE USED FOR DESIGN AS 2017 FBC - | | CODE IN EFFECT HAS CHANGED TO 2020 FBC - PLEASE REVISE | | THE DRAWINGS TO REFLECT THE CODE IN EFFECT. | | 3) PROVIDE SIGNAGE FOR THE FOLLOWING FIX - FBC 1011.7.4 | | ENCLOSURES UNDER EXTERIOR STAIRWAYS. | | THERE SHALL NOT BE ENCLOSED USABLE SPACE UNDER EXTERIOR | | EXIT STAIRWAYS UNLESS THE SPACE IS COMPLETELY ENCLOSED | | IN 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION. THE OPEN | | SPACE UNDER EXTERIOR STAIRWAYS SHALL NOT BE USED FOR | | ANY PURPOSE. |
|