Plan Review Notes
Plan Review Notes For Permit 20121129
Permit Number 20121129
Review Stop P
Sequence Number 3
Notes
Date Text
2021-04-29 17:24:473RD REVIEW FBC-2017 PLUMBING
 PERMIT- 20121129
 4/29/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 FAILED COMMENTS FROM THE 1ST AND 2ND REVIEW ARE LISTED
 BELOW WITH NOTES ADDED IN CAPS.
  
 1) FAILED. P0.1: PROVIDE PLUMBING FIXTURE CALCULATIONS
 IN COMPLIANCE WITH TABLE 403.3 FBC P. PROVIDE A
 SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED
 NUMBER OF REQUIRED FIXTURES. PLEASE NOTE THAT A SERVICE
 SINK IS A REQUIRED FOR MERCANTILE AND STORAGE
 OCCUPANCIES. REVISE THE PLANS ACCORDINGLY. THE COMMENT
 RESPONSE NARRATIVE STATES THE FIXTURES CALCULATIONS ARE
 ON A4.0.1 HOWEVER THEY ARE NOT SHOWN THERE.
  
 2) FAILED. SHEETS P0.1, P2.1 & P5.1: A GREASE
 INTERCEPTOR IS REQUIRED IN ACCORDANCE WITH 1003.3.1 FBC
 P TO RECEIVE THE DRAINAGE FROM THE 3-COMPARTMENT SINK
 (SK-3) AND THE SK SINKS. THE LARGE SK SINK APPEARS TO
 BE FOR FOOD PREP OR POT OR DISHWASHING WHICH REQUIRES
 AN INDIRECT WASTE PIPE. SIZING CALCULATIONS FOR THE
 INTERCEPTORS HAVE NOT BEEN PROVIDED. SEE COMMENT 4
 BELOW CONCERNING PLUMBING PIPING INSTALLATION AND
 SUBMIT MANUFACTURER'S SPECIFICATIONS.
  
 4) FAILED. P0.1: REFER TO SECTION 802.1 FBC P AND
 PROVIDE AN INDIRECT WASTE DETAIL FOR SK-3 AND THE LARGE
 SK SINK. INDIRECT WASTE DETAIL NOT PROVIDED. PLEASE
 NOTE THAT THE PLUMBING PLANS ARE SHOWING A DIRECT
 CONNECTION FROM THE 3-BAY SINK AND PREP SINK TO THE
 INTERCEPTORS WHICH IS NOT IN COMPLIANCE WITH SECTION
 802.1. PLEASE PROVIDE GREASE INTERCEPTOR PLUMBING
 DIAGRAMS FROM THE MANUFACTURER TO VERIFY COMPLIANCE-
 SECTION 1003.3.5.
  
 6) FAILED. P2.1 & P5.1: INDICATE HOW TRAP SEALS WILL BE
 PROVIDED FOR THE TRENCH DRAINS- SECTIONS 901.2 &
 1002.4.1 FBC P. TRAPS HAVE BEEN ADDED BUT NOT TRAP
 SEALS-
 1002.4.1 TRAP SEAL PROTECTION. TRAP SEALS OF EMERGENCY
 FLOOR DRAIN TRAPS AND TRAP SEALS SUBJECT TO EVAPORATION
 SHALL BE PROTECTED BY ONE OF THE METHODS IN SECTIONS
 1002.4.1.1 THROUGH 1002.4.1.4.
 1002.4.1.1 POTABLE WATER-SUPPLIED TRAP SEAL PRIMER
 VALVE. A POTABLE WATER-SUPPLIED TRAP SEAL PRIMER VALVE
 SHALL SUPPLY WATER TO THE TRAP. WATER-SUPPLIED TRAP
 SEAL PRIMER VALVES SHALL CONFORM TO ASSE 1018. THE
 DISCHARGE PIPE FROM THE TRAP SEAL PRIMER VALVE SHALL
 CONNECT TO THE TRAP ABOVE THE TRAP SEAL ON THE INLET
 SIDE OF THE TRAP.
  
 8) FAILED. A1.1.1, P2.1 & P5.1: THE FLOOR PLAN SHOWS AN
 ICE MACHINE WITH NO WASTE RECEPTOR TO RECEIVE THE
 DRAINAGE FROM THE ICE AND THE CONDENSATION. PLEASE
 INDICATE HOW THE DRAINAGE WILL BE DISCHARGED TO AN
 APPROVED LOCATION- SECTION 314.2 FBC P. THE RESPONSE
 NARRATIVE STATES THAT THE ICE MACHINE HAS BEEN REMOVED
 HOWEVER SHEET A1.1.1 IS SHOWING THE ICE MACHINE AND
 ALS1.1 SHOWS A LOBSTER TANK. THE PLANS ARE IN CONFLICT.
  
 9) PLEASE PROVIDE THE WATER HEATER COMPLAINCE DATA ON
 THE ENERGY EFFICIENCY REPORT- TABLE C404.2 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  