Plan Review Notes For Permit 20121118 |
Permit Number |
20121118 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-02-26 07:27:01 | PLAN REVIEW / BUILDING / GENERATOR | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER BUILDING - PX3169 | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | 1ST REVIEW | | | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | RE: SURVEY | | | | 1. R303.5.1 INTAKE OPENINGS: MECHANICAL AND GRAVITY | | OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS | | THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS | | CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, | | STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
|