2021-10-08 06:34:17SEE BELOW THE COMMENT FROM THE 2ND CYCLE REVIEW ABOUT
 THE BATHEXHAUST DUCTS PASSING THROUGH THE RATED TENANT
 SEPARATION WALLS. HOW ARE YOU PROTECTING THE DUCT
 PENETRATIONS OF THE RATED WALLS? FIRE DAMPERS?
  
 1) SHEETS M-1.3.03A AND M-1.3.04A HAVE THE BATH EXHAUST
 DUCT TRAVELING THROUGH THE APARTMENT SHAFT, THROUGH THE
 NEIGHBORING TENANTS EXHAUST SHAFT THEN THROUGH THE
 NEIGHBORING TENANT?S ROOM AND INTO ANOTHER EXHAUST
 SHAFT. THESE CHANGES WERE NOT CLOUDED OR MENTIONED IN
 THIS LATEST REVISION SCOPE. PLEASE EXPLAIN WHY THIS
 CHANGE IS OCCURRING AND HOW YOU WILL PROTECT THE
 PENETRATIONS OF THESE SHAFTS. FBC 717.5.3
  