Plan Review Notes
Plan Review Notes For Permit 20121101
Permit Number 20121101
Review Stop B
Sequence Number 3
Notes
Date Text
2021-10-15 11:53:06HOTEL REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2014 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
 1) DRAWING (A-4.2.01) SHOULD SHOW ROOF PLYWOOD AS FIRE
 RETARDANT PER FBC 603.1 (DRAWING A-0.0.02 SHOWS
 BUILDING CONSTRUCTION TYPE AS IIA)
 2) DRAWING (A-1.2.01) SHOWS ROOM 1204 TO BE 1 HR FIRE
 RATED - THE DOOR SCHEDULE DOES NOT SHOW THE DOOR HOURLY
 FIRE RATING AND THE SELF CLOSING AND LATCHING
 REQUIREMENT FBC TABLE 716.5 AND 716.5.9
  
  