Date |
Text |
2021-06-28 09:12:12 | 1) SHT. A-1.3.01 - THE SINK IN ONE OF THE TREATMENT |
| ROOMS AND ONE OF THE COUPLE'S SUITES AT THE SPA SHALL |
| COMPLY WITH FBC-ACCESSIBILITY SECS. 212.3, 606.1. THE |
| RESPONSE NARRATIVE REFERS TO STAFFING BY "ABLE-BODIED" |
| EMPLOYEES WHICH HAS NOTHING TO DO WITH THE HEIGHT OF |
| THE SINKS IN THESE ROOMS. SHOW COMPLIANCE ON THE PLANS |
| WITH THE ACCESSIBILITY REQUIREMENTS FOR THE SINKS. 2ND |
| REQUEST. |
| 2) THE FOLLOWING SHEETS DO NOT BEAR THE DIGITAL |
| SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL AS |
| REQUIRED BY F.A.C. 61G15-23.0001, 61G15-23.004 - |
| P-0.0.00, P-1.1.00, P-1.1.01A, P-1.1.01B, P-1.3.05B, |
| P-1.5.01, P-3.0.02B, P-3.0.08. 2ND REQUEST. |
| 3) SHT. P-1.1.00 - INDICATE ON THE PLAN WHAT STANDARD |
| WAS USED FOR THE SIZING OF THE GREASE INTERCEPTORS. |
| REFER TO FBC-PLUMBING SECS.1003.2, 1003.3.4. 2ND |
| REQUEST. |
| 4) PLACE MATCHLINES ON THE PLUMBING DRAWINGS ALONG WITH |
| THE CORRELATING PAGE THAT SHOWS THE CONTINUATION OF THE |
| PIPING.THE WORD "MATCHLINE " WAS PLACED ON THE PLUMBING |
| SHEETS WITH NO CORRESPONDING REFERENCE SHEET. 2ND |
| REQUEST. |
| 5) SHT. P-1.5.05 - A HOT WATER RECIRCULATION LINE IS |
| REQUIRED IN THE BANQUET KITCHEN. THERE IS NO HOT WATER |
| RECIRCULATION LINE SHOWN ON THE FLOOR PRESSURE PLAN FOR |
| THE BANQUET KITCHEN ON SHT.P-1.401A. FBC-PLUMBING |
| SEC.607.2. 2ND REQUEST. |
| 6) SHT. P-1.5.06 - THE COFFEE AND TEA BREWERS, WATER |
| FILTERS AND ICE MAKER SHALL BE EQUIPPED WITH INDIVIDUAL |
| BACKFLOW PREVENTION DEVICES COMPLYING WITH ASSE 1024 |
| PER FBC-PLUMBING SEC. 608.3.THE SODA DISPENSER SHALL BE |
| EQUIPPED WITH A BACKFLOW PREVENTER COMPLYING WITH ASSE |
| 1022. THE DISHWASHER SHALL BE EQUIPPED WITH A BACKFLOW |
| PREVENTION DEVICE COMPLYING WITH ASSE 1020. 2ND |
| REQUEST. |
| 7)SHT. P-1.5.07 - DETAIL #1 - SHOW THE CONTINUATION |
| POINT OF THE GAS LINE ON THE ENLARGED KITCHEN PRESSURE |
| PLAN. WPB AMEND. TO FBC SEC. 107.2.1. |
| 8) SHT.P-3.0.01 - A RISER TAG ON THE PLAN CALLS OUT |
| SAN. RISERS 26 - 28 BUT THERE IS NO RISER SHOWN. |
| CLARIFY. |
| 9) SHT. P-3.0.09 - THERE ARE SOME DOWNSPOUTS THAT ARE |
| NOT SIZED, PART OF THE RISER IS CUT OFF ON THE LEFT |
| SIDE AND RIGHT SIDE OF THE DRAWING. OF THE DRAWING, |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |