Plan Review Notes
Plan Review Notes For Permit 20121101
Permit Number 20121101
Review Stop P
Sequence Number 2
Notes
Date Text
2021-06-28 09:12:121) SHT. A-1.3.01 - THE SINK IN ONE OF THE TREATMENT
 ROOMS AND ONE OF THE COUPLE'S SUITES AT THE SPA SHALL
 COMPLY WITH FBC-ACCESSIBILITY SECS. 212.3, 606.1. THE
 RESPONSE NARRATIVE REFERS TO STAFFING BY "ABLE-BODIED"
 EMPLOYEES WHICH HAS NOTHING TO DO WITH THE HEIGHT OF
 THE SINKS IN THESE ROOMS. SHOW COMPLIANCE ON THE PLANS
 WITH THE ACCESSIBILITY REQUIREMENTS FOR THE SINKS. 2ND
 REQUEST.
 2) THE FOLLOWING SHEETS DO NOT BEAR THE DIGITAL
 SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL AS
 REQUIRED BY F.A.C. 61G15-23.0001, 61G15-23.004 -
 P-0.0.00, P-1.1.00, P-1.1.01A, P-1.1.01B, P-1.3.05B,
 P-1.5.01, P-3.0.02B, P-3.0.08. 2ND REQUEST.
 3) SHT. P-1.1.00 - INDICATE ON THE PLAN WHAT STANDARD
 WAS USED FOR THE SIZING OF THE GREASE INTERCEPTORS.
 REFER TO FBC-PLUMBING SECS.1003.2, 1003.3.4. 2ND
 REQUEST.
 4) PLACE MATCHLINES ON THE PLUMBING DRAWINGS ALONG WITH
 THE CORRELATING PAGE THAT SHOWS THE CONTINUATION OF THE
 PIPING.THE WORD "MATCHLINE " WAS PLACED ON THE PLUMBING
 SHEETS WITH NO CORRESPONDING REFERENCE SHEET. 2ND
 REQUEST.
 5) SHT. P-1.5.05 - A HOT WATER RECIRCULATION LINE IS
 REQUIRED IN THE BANQUET KITCHEN. THERE IS NO HOT WATER
 RECIRCULATION LINE SHOWN ON THE FLOOR PRESSURE PLAN FOR
 THE BANQUET KITCHEN ON SHT.P-1.401A. FBC-PLUMBING
 SEC.607.2. 2ND REQUEST.
 6) SHT. P-1.5.06 - THE COFFEE AND TEA BREWERS, WATER
 FILTERS AND ICE MAKER SHALL BE EQUIPPED WITH INDIVIDUAL
 BACKFLOW PREVENTION DEVICES COMPLYING WITH ASSE 1024
 PER FBC-PLUMBING SEC. 608.3.THE SODA DISPENSER SHALL BE
 EQUIPPED WITH A BACKFLOW PREVENTER COMPLYING WITH ASSE
 1022. THE DISHWASHER SHALL BE EQUIPPED WITH A BACKFLOW
 PREVENTION DEVICE COMPLYING WITH ASSE 1020. 2ND
 REQUEST.
 7)SHT. P-1.5.07 - DETAIL #1 - SHOW THE CONTINUATION
 POINT OF THE GAS LINE ON THE ENLARGED KITCHEN PRESSURE
 PLAN. WPB AMEND. TO FBC SEC. 107.2.1.
 8) SHT.P-3.0.01 - A RISER TAG ON THE PLAN CALLS OUT
 SAN. RISERS 26 - 28 BUT THERE IS NO RISER SHOWN.
 CLARIFY.
 9) SHT. P-3.0.09 - THERE ARE SOME DOWNSPOUTS THAT ARE
 NOT SIZED, PART OF THE RISER IS CUT OFF ON THE LEFT
 SIDE AND RIGHT SIDE OF THE DRAWING. OF THE DRAWING,
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  