Date |
Text |
2021-06-16 06:45:45 | 2ND REVIEW FBC-2020 MECHANICAL |
| PERMIT-20121101 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEETS M-1.3.03A AND M-1.3.04A HAVE THE BATH EXHAUST |
| DUCT TRAVELING THROUGH THE APARTMENT SHAFT, THROUGH THE |
| NEIGHBORING TENANTS EXHAUST SHAFT THEN THROUGH THE |
| NEIGHBORING TENANT?S ROOM AND INTO ANOTHER EXHAUST |
| SHAFT. THESE CHANGES WERE NOT CLOUDED OR MENTIONED IN |
| THIS LATEST REVISION SCOPE. PLEASE EXPLAIN WHY THIS |
| CHANGE IS OCCURRING AND HOW YOU WILL PROTECT THE |
| PENETRATIONS OF THESE SHAFTS. FBC 717.5.3 |
| |
| 2) SHEET M-0.0.02: IN THE EXHAUST FAN SCHEDULE CHART |
| TE-1, TE-2 AND TE-3 WERE NOT MENTIONED IN THE SCOPE OF |
| THIS REVISION NOR WERE THEY CLOUDED TO INDICATE A |
| CHANGE. PLEASE SHOW THESE ON THE ROOF PLAN. FBC 107.2.1 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| MICHAEL EDWARDS |
| MECHANICAL EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL. 33401 |
| 561-805-6728 |
| [email protected] |
| |