Plan Review Notes For Permit 20121101 |
Permit Number |
20121101 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2021-07-02 14:42:39 | HOTEL REVISION 9 | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2014 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - | | 1) DRAWING (A-4.2.01) SHOULD SHOW ROOF PLYWOOD AS FIRE | | RETARDANT PER FBC 603.1 (DRAWING A-0.0.02 SHOWS | | BUILDING CONSTRUCTION TYPE AS IIA) | | 2) DRAWING (S-2.04BT) SHOWS NOTE NUMBER (16) AS A NOTE | | FOR 4 X 10 LUMBER WHICH HAS BEEN CHANGED TO 2 X 10 | | LUMBER - PLEASE REVISE THE NOTES. | | 3) 1ST FLOOR LIFE SAFETY FLOOR PLAN SHOWS EGRESS PATH | | (RED DOTTED LINE) THROUGH THE WALL IN THE (1123) | | DINING/LOUNGE. | | | | |
|