2021-04-22 12:54:231) SUBMIT A FLOOR PLAN SHOWING THE PIPING FOR THE GAS
 SYSTEM. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHT. P-3.0.07 - UNIONS ARE REQUIRED WITHIN ONE FOOT
 UPSTREAM OR DOWNSTREAM OF ALL GAS PRESSURE REGULATORS.
 FBC-FUEL GAS SEC.410.2 (7).
 3) SHT. P-3.0.08 HAS A NAMING CONVENTION OF "NATURAL
 GAS" BUT THE PLAN IS OR A CONDENSATE RISER. PLEASE
 REVISE.
  